Eaton DC1 Variable frequency drive, 115 V AC, single-phase, 5.8 A, 1.1 kW, IP66/NEMA 4X, Brake chopper, 7-digital display assembly, Additional PCB protection, UV resistant, FS2
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199397
|
EAN |
4015081977864
|
Product Length/Depth |
182 mm
|
Product Height |
257 mm
|
Product Width |
188 mm
|
Product Weight |
3.5 kg
|
Certifications |
IEC/EN 61800-5-1
RCM UL 508C UL Category Control No.: NMMS, NMMS7 EAC UkrSEPRO UL UL Listed CE marking IEC/EN 61800-3 IEC/EN 61800-2 RoHS, ISO 9001 CSA-C22.2 No. 14 UL File No.: E172143 UL report applies to both US and Canada IEC/EN61800-5 CE CUL Certified by UL for use in Canada |
Features |
Parameterization: drivesConnect
Parameterization: Fieldbus Parameterization: Keypad Parameterization: drivesConnect mobile (App) |
Fitted with: |
Breaking resistance
Internal DC link UV resistance Control unit IGBT inverter 7-digital display assembly Brake chopper Additional PCB protection PC connection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
No
|
Operating mode |
U/f control
Synchronous reluctance motors Sensorless vector control (SLV) Speed control with slip compensation BLDC motors PM motors |
Frame size |
FS2
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-20 °C
|
Mains voltage - max |
115 V
|
Output voltage - max |
250 V
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
1.1 kW
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Application in industrial area permitted |
Yes
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Switch-on threshold for the braking transistor |
390 VDC
|
Voltage rating - max |
120 V
|
Mounting position |
Vertical
|
Communication interface |
OP-Bus (RS485), built in
SmartWire-DT, optional Modbus RTU, built in CANopen®, built in |
Converter type |
U converter
|
Degree of protection |
IP66
NEMA 4X |
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
1.5 HP
|
Braking resistance |
100 Ω
|
Input current ILN at 150% overload |
21.9 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
4.6 A
|
Protocol |
MODBUS
CAN EtherNet/IP Other bus systems |
Overload current IL at 150% overload |
8.7 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
System configuration type |
AC supply systems with earthed center point
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Cable length |
150 m, unscreened, maximum permissible cable length
300 m, unscreened, with motor choke, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible cable length 100 m, screened, maximum permissible cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
230 V AC, 3-phase
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Number of outputs (digital) |
1
|
Starting current - max |
175 % IH
|
Number of phases (input) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Power consumption |
44 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
4.8 mA
|
Mains voltage - min |
110 V
|
Nominal output current I2N |
5.8 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
1.1 kW
|
Output at quadratic load at rated output voltage - max |
1.1 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
5.8 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational voltage |
115 V AC, 1-phase
|
Short-circuit protection rating |
35 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|