Eaton XIOC Digital input card for XC100/200, 24 V DC, 16DI
Product Name |
Eaton XIOC Accessory Input card
|
Catalog Number |
257892
|
Model Code |
XIOC-16DI
|
EAN |
4015082578923
|
Product Length/Depth |
100 mm
|
Product Height |
95 mm
|
Product Width |
30 mm
|
Product Weight |
0.135 kg
|
Certifications |
UL Category Control No.: NRAQ
CSA UL File No.: E135462 CE UL508 CSA Class No.: 2252-01 CSA-C22.2 No. 0-M CSA-C22.2 No. 142-M EN 50178 CSA File No.: 012528 IEC/EN 61131-2 UL |
Electric connection type |
Screw-/spring clamp connection
|
Admissible range |
20.4 – 28.8 V (11.8 – 14.4 V), Power supply
|
Current consumption |
51 mA, with fitted modules
|
Degree of protection |
IP20
|
Number of channels |
16, Input
|
Overvoltage category |
II
|
Pollution degree |
2
|
Protection |
Protection class: 1
|
Repetition rate |
1 s
|
Residual ripple |
≤ 5 %
|
Switching level |
≤ 15 V DC, ON, Voltage level to IEC 61131-2, limit value type 1, Inputs
≤ 5 V DC, OFF, Voltage level to IEC 61131-2, limit value type 1, Inputs |
Type |
Digital module
|
Used with |
XC100/200 (expandable with up to 15 XI/OC modules)
|
Voltage type |
DC
|
Impact resistance |
500 g/⌀ 50 mm ±25 g
|
Shock resistance |
15 g, Mechanical, Shock duration 11 ms
|
Vibration resistance |
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm |
Ambient operating temperature - min |
0 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Emitted interference |
Class A (according to DIN/EN 55011/22)
|
Voltage dips |
10 ms
|
Terminals |
|
Power loss |
Max. 1.6 W
|
Rated operational voltage |
24 (12) V DC
|
Short-circuit protection |
Yes, Outputs
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
20.4 VDC
|
Supply voltage at DC - max |
28.8 VDC
|
LED indicator |
Status indication: Green LED
|
Delay time |
≤ 5 ms typ., Digital inputs 24 V DC, Delay time from 0 to 1, Debounce ON
≤ 5 ms (normally 4 ms), Debounce ON |
Input |
Voltage (DC)
16 Inputs (24 V DC) |
Input current |
4 mA
|
Input current at signal 1 |
4 mA
|
Input impedance |
5.9 kΩ
|
Input voltage |
24 V DC (modules)
|
Number of inputs (digital) |
16
|
Number of outputs (digital) |
0
|
Output current |
0 A
|
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Potential isolation |
Digital inputs: Opto-isolated
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
1.6 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|