Eaton Moeller® series ZW7 Current transformer-operated overload relay, 270-400A, 1N/O+1N/C
Product Name |
Eaton Moeller® series ZW7 Current transformer-operated overload relay
|
Catalog Number |
045329
|
EAN |
4015080453291
|
Product Length/Depth |
162.5 mm
|
Product Height |
97 mm
|
Product Width |
200.5 mm
|
Product Weight |
0.639 kg
|
Certifications |
CSA-C22.2 No. 14
UL 508 IEC/EN 60947 UL File No.: E29184 CE CSA File No.: 012528 UL VDE 0660 CSA UL Category Control No.: NKCR CSA Class No.: 3211-03 IEC/EN 60947-4-1 |
Catalog Notes |
Rated operational current: Switch-on and switch-off conditions based on DC-13, time constant as specified.
|
Features |
Trip-free release
Test/off button Reset pushbutton manual/auto Protection with heavy starting duty |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Class |
Other
|
Opening diameter |
27 mm
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Rated impulse withstand voltage (Uimp) |
4000 V (auxiliary and control circuits)
8000 V AC |
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
1.5 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
0.9 A
|
Rated operational current (Ie) at DC-13, 110 V |
0.4 A
|
Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.2 A
|
Rated operational current (Ie) at DC-13, 24 V |
0.9 A
|
Rated operational current (Ie) at DC-13, 60 V |
0.75 A
|
Rated operational current for specified heat dissipation (In) |
400 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Stripping length (control circuit cable) |
8 mm
|
Voltage rating - max |
600 VAC
|
Product category |
ZW7 current transformer-operated overload relays
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Adjustable current range - max |
400 A
|
Adjustable current range - min |
270 A
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
25 °C
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
6 A
|
Equipment heat dissipation, current-dependent Pvid |
7.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
2.5 W
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
1
|
Number of auxiliary contacts (normally open contacts) |
1
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally open contacts) |
1
|
Overload release current setting - max |
400 A
|
Overload release current setting - min |
270 A
|
Rated operational voltage (Ue) - max |
690 V
|
Rated operational current (Ie) at AC-15, 120 V |
1.5 A
|
Electrical connection type of main circuit |
Screw connection
|
Reset function |
Push-button
Automatic |
Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver |
Mounting position |
As required
|
Mounting method |
Separate mounting
Separate positioning |
Degree of protection |
IP00
|
Overvoltage category |
III
|
Safe isolation |
440 V AC, Between auxiliary contacts and main contacts, According to EN 61140
240 V AC, Between auxiliary contacts, According to EN 61140 440 V AC, Between main circuits, According to EN 61140 |
Screw size |
M3.5, Terminal screw
|
Shock resistance |
10 g, Mechanical, Sinusoidal, Shock duration 10 ms
|
Short-circuit protection |
With overload relay in conjunction with a transformer as required for the contactor, Max. Fuse, Main conducting paths
|
Switching capacity (auxiliary contacts, pilot duty) |
R300, DC operated (UL/CSA)
B600 at opposite polarity, AC operated (UL/CSA) B300 at opposite polarity, AC operated (UL/CSA) |
Short-circuit protection rating |
Max. 6 A gG/gL, Fuse, Auxiliary contacts
|
Suitable for |
Branch circuits, (UL/CSA)
|
Temperature compensation |
Continuous
|
Terminal capacity (flexible with ferrule) |
2 x (0.75 - 2.5) mm²
1 x (0.75 - 2.5) mm² |
Terminal capacity (solid) |
1 x (0.75 - 4) mm²
2 x (0.75 - 4) mm² |
Terminal capacity (solid/stranded AWG) |
2 x (18 - 14)
|
Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
|
Rated frequency - min |
50 Hz
|
Rated frequency - max |
60 Hz
|