Descargar documento () de 20

170821

Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection. RCD/MCB, 13A, 100mA, MCB trip type C, 2p, RCCB trip type: A, G

General specifications

Product Name
Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection
Catalog Number
170821
EAN
4015081673889
Product Length/Depth
80 mm
Product Height
75.5 mm
Product Width
35 mm
Product Weight
0.25 kg
Compliances
RoHS conform
Certifications
CE
EN45545-2
IEC 61373

Programa de entrega

Basic function
Combined RCD/MCB devices
Number of poles (total)
2
Type
RCBO
Application
Switchgear for industrial and advanced commercial applications
Tripping characteristic
C
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Sensitivity type
Pulse-current sensitive
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.

Datos técnicos - eléctricos

Sensitivity type
Pulse-current sensitive
Type
RCBO

Verificación de diseño según IEC/EN 61439 - Datos técnicos

10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Operating ambient temperature - min
-25 °C
Operating ambient temperature - min
-25 °C

Verificación de diseño según IEC/EN 61439

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Impulse withstand current
Partly surge-proof, 250 A
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.

Datos técnicos ETIM 7.0

Release characteristic
C
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Current limiting class
3
Rated switching capacity (IEC/EN 61009)
10 kA
Rated short-circuit breaking capacity (EN 60947-2)
0 kA
Disconnection characteristic
Undelayed
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Width in number of modular spacings
2
Heat dissipation capacity
0 W
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Pollution degree
2
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Built-in depth
75.5 mm
Surge current capacity
0.25 kA

Exportar especificación del producto