Eaton XN-322 Analog I/O module, 2 analog inputs and 2 analog outputs, +/-10 V, Uref
Product Name |
Eaton XN-322 I/O module
|
Catalog Number |
183181
|
EAN |
4015081781140
|
Product Length/Depth |
104.2 mm
|
Product Height |
16.8 mm
|
Product Width |
80.3 mm
|
Product Weight |
0.055 kg
|
Certifications |
UL File No.: E135462
IEC/EN 61000-6-2 CE IEC/EN 61131-2 cULus IEC/EN 61000-6-4 |
Used with |
XN300
XN-312-… |
Type |
|
Features |
Analog outputs configurable
Output, voltage Input, voltage Analog inputs configurable Fieldbus connection over separate bus coupler possible Input signal, configurable |
Air discharge |
8 kV
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Plug-in connection
|
Fitted with: |
1 kHz, third-order low-pass input filter
Parameterizable Software input filter |
Pollution degree |
3
|
Accuracy |
± 0.5 % of full scale, Analog outputs
± 0.3 % of full scale, Voltage measurement |
Burst impulse |
1 kV, Signal cable
2 kV, Supply cable |
Number of channels |
2, Analog Inputs
|
Resolution |
|
Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 |
Air pressure |
795 - 1080 hPa (operation)
|
Explosion safety category for dust |
None
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Resolution of the analog inputs |
16 Bit
|
Resolution of the analog outputs |
12 Bit
|
Static heat dissipation, non-current-dependent Pvs |
1.952 W
|
Stripping length (main cable) |
10 mm
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
30 VDC
|
Supply voltage at DC - min |
18 VDC
|
Product category |
XN-322 analog input and output module
|
Power consumption |
1.2 W
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Input |
2 Analog inputs (±10 V, Uref)
|
Output voltage |
-10 - 10 V DC (analog outputs)
|
Explosion safety category for gas |
None
|
Mounting method |
Rail mounting possible
|
Current consumption |
55 mA (typ.), for +5 V power supply (internal), Power supply - Input
45 mA (typ.), for +24 V, Power supply - Input |
Voltage type |
DC
|
Mounting position |
Horizontal
|
Output |
2 Analog Outputs (±10 V)
|
Input voltage |
Max. 14 V DC
|
Contact discharge |
4 kV
|
Overvoltage category |
III
|
Capacitive load |
0.1 µF, Analog outputs
|
Surge rating |
1 kV, Signal cable, unbalanced, EMC
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC |
Emitted interference |
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency) |
Potential isolation |
Analog inputs: no
Sensor/transmitter supply: no |
Electromagnetic fields |
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
Load current |
Not specified by plug manufacturer
|
Number of inputs (analog) |
2
|
Radiated RFI |
10 V
|
Protocol |
Other bus systems
|
Relative humidity |
0 - 95 % (non-condensing)
|
Connection type |
2 conductors, Voltage measurement
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction 2 conductors, Analog outputs, Output voltage |
Rated control supply voltage |
10 V (Sensor/transmitter supply)
|
Rated operational current (Ie) |
Max. 0.0083 A (supply output)
|
Rated operational voltage |
160 V (terminations)
|
Refresh time |
1 ms (analog inputs, all channels)
|
Degree of protection |
IP20
NEMA 1 |
Gauge pin |
A1 (according to IEC/EN 60947-1)
|
Short-circuit current |
30 mA, per channel, Analog outputs
|
Resistive load |
> 5000 Ω, analog outputs
|
Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
Shock resistance |
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
|
Short-circuit protection |
Yes, Short-circuit strength, Analog outputs
|
Insulating material group |
I
|
Voltage measurement |
± 12 V DC, Common-mode range
Open wire monitoring. -10 - 10 V DC, Measurement range > 10 MΩ, Input resistance The channels can also be used as potentiometer inputs. |
System accessory |
Yes
|
Terminal capacity |
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.2 - 1.5 mm², flexible without ferrule, H07V-K 24 - 16 AWG 0.2 - 1.5 mm², solid, H07V-U 0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
Value refresh time/cycle time |
Min. 1 / 1 ms (per channel / all channels), Analog Inputs
|
Value representation |
SIGNED16, mV, Voltage measurement
|
Voltage dips |
Voltage dips: 10 ms/Voltage fluctuations: Yes
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
0 °C
|
Ambient storage temperature - max |
85 °C
|
Ambient storage temperature - min |
-20 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
1.018 W
|
Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Limit frequency |
1 kHz (third-order low-pass filter)
|
Measured variables |
Voltage or potentiometer
|