Eaton Moeller series NZM - Molded Case Circuit Breaker. Connection, SmartWire-DT, for NZM
| Product Name |
Eaton Moeller series NZM electronic accessory
|
| Catalog Number |
135530
|
| EAN |
4015081323166
|
| Product Length/Depth |
90 mm
|
| Product Height |
102 mm
|
| Product Width |
35 mm
|
| Product Weight |
0.18 kg
|
| Compliances |
IEC
RoHS conform |
| Certifications |
UL CSA08 (request filed)
IEC/EN 61131-2 EN 50178 |
| Model Code |
NZM-XSWD-704
|
| Used with |
SmartWire-DT interface for NZM circuit breakers
|
| Special features |
|
| Type |
Accessory
|
| Features |
Fieldbus connection over separate bus coupler possible
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Potential separation
|
| Frame |
NZM2/3/4
|
| Pollution degree |
2 (EMC)
|
| Burst impulse |
2 kV
1 kV |
| Connection to SmartWire-DT |
Plug, 8-pole connection
Connection to SmartWire-DT Green LED (status SmartWire-DT) Automatic setting the baud rate SmartWire-DT slave (station type) Connection plug: external device plug SWD4-8SF2-5 |
| Isolation |
Outputs to SmartWire-DT (potential isolation)
Inputs for SmartWire-DT (potential isolation) |
| Accessory/spare part type |
Diagnostics and communication
|
| Category (EN 954-1) |
B
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Mounting method |
Top-hat rail IEC/EN 60715, 35 mm
Wall mounting/direct mounting Rail mounting possible |
| Voltage type |
DC
|
| Mounting position |
Vertical
|
| Overvoltage category |
II
|
| Dimensions |
35 mm x 90 mm x 101 mm
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Terminal connection for I/O sensor |
Push in terminals
|
| Vibrations at constant acceleration 1 g (IEC/EN 61131-2:2008) |
8.4 Hz - 150 Hz
|
| Vibrations at constant amplitude 3.5 mm (IEC/EN 61131-2:2008) |
5 Hz - 8.4 Hz
|
| Voltage range of type 1 digital inputs |
Low ≤ 5V DC; High ≥ 15V DC
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Drop height (IEC/EN 60068-2-31) |
50 mm
|
| EMC of electromagnetic fields at 1.4 - 2 GHz (IEC/EN 61131-2:2008) |
3 V/m
|
| EMC of electromagnetic fields at 2 - 2.7 GHz (IEC/EN 61131-2:2008) |
1 V/m
|
| EMC of electromagnetic fields at 80 - 1000 MHz (IEC/EN 61131-2:2008) |
10 V/m
|
| EMC of electrostatic air discharge level 3 (IEC/EN 61131-2:2008) |
8 KV
|
| EMC of electrostatic contact discharge level 2 (IEC/EN 61131-2:2008) |
4 KV
|
| EMC of radiated RFI level 3 (IEC/EN 61131-2:2008) |
10 V
|
| Input current of digital inputs |
4 mA
|
| Relative humidity |
5 - 95 %
|
| Degree of protection |
IP20
|
| Protocol |
Other bus systems
|
| Overload proof of digital semi-conductor outputs |
Yes, with diagnostics
|
| Terminal capacity (cable) |
0.25 mm² - 1.5 mm² with ferrule
|
| Terminal capacity (solid wire) |
0.2 mm² - 1.5 mm² (AWG 24 - AWG 16)
|
| Functions |
SmartWire-DT module NZM circuit breakers
SmartWire-DT slave (product range) The module implements the data connection between the NZM2/3/4 with electronic release and SmartWire-DT. |
| Digital input delay |
High to low < 0.2 ms
Low to High typ. < 0.2 ms |
| Shock resistance |
9 impacts (IEC 60068-2-27)
|
| Short-circuit tripping current |
Max. 1.2 over 3 ms (digital semi-conductor outputs)
|
| System accessory |
No
|
| Number of inputs (digital) |
8
|
| Lamp load of digital semi-conductor outputs |
3 W
|
| Number of outputs (semiconductor) |
4
|
| Packaged free fall height (IEC/EN 60068-2-32) |
0.3 m
|
| Messages |
Actual current value in A
Load warnings Actual settings of the rotary coding switches Reason for last trip Switch type Status data NZM: ON/OFF/TRIPPED |
| Output current of digital semiconductor outputs |
Normally 0.5 A at 24 V DC
|
| Supply voltage at AC, 50 Hz - max |
0 V
|
| Supply voltage at AC, 50 Hz - min |
0 V
|
| Supply voltage at AC, 60 Hz - max |
0 V
|
| Supply voltage at AC, 60 Hz - min |
0 V
|
| Supply voltage at DC - max |
24 V
|
| Supply voltage at DC - min |
24 V
|