Eaton Moeller® series PKE32 Motor-protective circuit-breaker, Complete device with standard knob, Electronic, 8 - 36 A, With overload release
| Product Name |
Eaton Moeller® series PKE System-protective circuit-breaker
|
| Catalog Number |
170128
|
| EAN |
4015081666270
|
| Product Length/Depth |
101 mm
|
| Product Height |
102.5 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.436 kg
|
| Certifications |
IEC/EN 60947
VDE 0660 |
| Catalog Notes |
This is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.
|
| Model Code |
PKE32/XTU-36-SOND533
|
| Features |
Phase-failure sensitivity (trip blocks)
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Standard knob
|
| Operating frequency |
60 Operations/h
|
| Pollution degree |
3
|
| Lifespan, mechanical |
50,000 Operations (Main conducting paths)
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Actuator type |
Turn button
|
| Adjustment range undelayed short-circuit release - max |
496 A
|
| Adjustment range undelayed short-circuit release - min |
496 A
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Equipment heat dissipation, current-dependent Pvid |
14.4 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
4.8 W
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Altitude |
Max. 2000 m
|
| Device construction |
Built-in device fixed built-in technique
|
| Connection |
Screw terminals
|
| Electrical connection type of main circuit |
Screw connection
|
| Current flow times - min |
900 (Class 15) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths Note: Going below the minimum current flow time can cause overheating of the load (motor). 500 (Class 5) AC-4 cycle operation, Main conducting paths For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods. 700 (Class 10) AC-4 cycle operation, Main conducting paths |
| Overvoltage category |
III
|
| Cut-out periods - min |
≤ 500 ms, main conducting paths, AC-4 cycle operation
|
| Degree of protection |
Terminals: IP00
IP20 |
| Number of poles |
Three-pole
|
| Lifespan, electrical |
50,000 operations (at 400V, AC-3)
|
| Shock resistance |
25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
| Functions |
Motor protection for heavy starting duty
Phase failure sensitive Overload release Motor protection |
| Terminal capacity (solid/stranded AWG) |
14 - 10
|
| Switching capacity |
36 A, AC-3 up to 690 V
|
| Overload release current setting - max |
36 A
|
| Overload release current setting - min |
36 A
|
| Rated frequency - max |
60 Hz
|
| Rated frequency - min |
50 Hz
|
| Rated operational voltage (Ue) - max |
690 V
|
| Rated operational voltage (Ue) - min |
690 V
|
| Rated operational current for specified heat dissipation (In) |
36 A
|
| Rated operational power at AC-3e, 220/230 V, 50 Hz |
7.5 kW
|
| Rated operational power at AC-3e, 380/400 V, 50 Hz |
18.5 kW
|
| Rated uninterrupted current (Iu) |
36 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| Product category |
Motor protective circuit breaker
|
| Rated operational power at AC-3e, 440 V, 50 Hz |
18.5 kW
|
| Rated operational power at AC-3e, 500 V, 50 Hz |
22 kW
|
| Rated operational power at AC-3e, 690 V, 50 Hz |
30 kW
|
| Rated short-circuit breaking capacity Icu at 400 V AC |
0 kA
|
| Suitable for |
Also motors with efficiency class IE3
|
| Short-circuit release |
Basic device, fixed 20 x Iu, Trip Blocks
Delayed approx. 60 ms, Trip blocks Trip block fixed 496 A ± 20% tolerance, Trip blocks |
| Terminal capacity (solid) |
1 x (1 - 6) mm²
2 x (1 - 6) mm² |
| Rated operational current (Ie) |
36 A
|
| Temperature compensation |
Up to 55 °C (Operating range), residual error for T > 40°
|
| Tightening torque |
1 Nm, Screw terminals, Control circuit cables
1.7 Nm, Screw terminals, Main cable |
| Switch off technique |
Electronic
|
| Terminal capacity (flexible with ferrule) |
1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm², ferrule to DIN 46228 |
| Resistance per pole |
2.6 mΩ
|