Eaton EU2E SmartWire-DT IP67 T-Connector analog module, two configurable Pt100/Pt1000/Ni1000 temperature inputs, two M12 I/O sockets
| Product Name |
Eaton EU2E Analog module
|
| Catalog Number |
174733
|
| EAN |
4015081712199
|
| Product Length/Depth |
98 mm
|
| Product Height |
20.1 mm
|
| Product Width |
56.9 mm
|
| Product Weight |
0.085 kg
|
| Certifications |
IEC/EN 61131-2
UL UL File No.: E170645 CSA |
| Model Code |
EU2E-SWD-2PT
|
| Type |
Analog modules
|
| Features |
Analog outputs configurable
Input signal, configurable Fieldbus connection over separate bus coupler possible Input, resistance thermometer Analog inputs configurable |
| Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Screw connection
|
| Fitted with: |
Temperature sensors PT100, PT1000 and Ni1000
Display mode for temperatures (°C, °F, raw value) |
| Pollution degree |
3
|
| Burst impulse |
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 |
| Resolution |
0.1 °C, Temperature inputs
|
| Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 |
| Connection to SmartWire-DT |
Yes
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Explosion safety category for dust |
None
|
| Operating temperature - max |
70 °C
|
| Operating temperature - min |
-100 °C
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Resolution of the analog inputs |
12 Bit
|
| Resolution of the analog outputs |
0 Bit
|
| Static heat dissipation, non-current-dependent Pvs |
0.9 W
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 60 Hz - max |
0 VAC
|
| Supply voltage at AC, 60 Hz - min |
0 VAC
|
| Supply voltage at DC - max |
0 VDC
|
| Supply voltage at DC - min |
0 VDC
|
| Product category |
SmartWire-DT slave
|
| Power consumption |
0.9 W
|
| Environmental conditions |
Condensation: permissible
|
| Input |
Inputs, configurable (PT100, PT1000, Ni1000)
|
| Explosion safety category for gas |
None
|
| Mounting method |
Rail mounting possible
Wall mounting/direct mounting DIN rail Mounting section (Clip M20) Screw fixing (M4) |
| Current consumption |
37 mA, SmartWire-DT network
|
| Voltage type |
DC
|
| Mounting position |
As required
|
| Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
| Overvoltage category |
II
|
| Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
| Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
| Surge rating |
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
| Potential isolation |
Inputs for SmartWire-DT: no
Input to input: no |
| Power loss |
0.9 W
|
| Conversions |
250 ms, Temperature inputs
|
| Electromagnetic fields |
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) |
| Number of inputs (analog) |
2
|
| Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Protocol |
Other bus systems
|
| Radio interference class |
Class A (EN 55011)
|
| Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
| Connection type |
SWD-OUT: M12 socket (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor SWD-IN : M12 plug (A-keyed), 5 pole |
| Repetition accuracy |
0.5 % (Temperature inputs)
|
| Data transfer rate |
2 MBit/s, SmartWire-DT
Setting automatically |
| Degree of protection |
IP69K
NEMA 4X |
| Station |
SmartWire-DT slave, SmartWire-DT network
|
| Shock resistance |
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
| Functions |
For connection of analog I/O signals
Adjustable parameter settings |
| System accessory |
Yes
|
| Total error |
± 1 %, Temperature Inputs
|
| LED indicator |
Status indication of SmartWire-DT network: Green LED
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
0
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
0
|