178795
Mudeli kood: XN-322-1CNT-8DIO

Eaton XN-322 Counter module, 4 digital inputs +24 V , 4 digital outputs, +24 V/ 2A, 1 incremental encoder input (RS422 or TTL) up to 500 kHz, 16 bits

General specifications

Product Name
Eaton XN-322 Counter module
Catalog Number
178795
EAN
7640130098299
Product Length/Depth
104.2 mm
Product Height
16.8 mm
Product Width
80.3 mm
Product Weight
0.061 kg
Certifications
UL File No.: E135462
CE
cULus
EN 61131-2
EN 61000-6-2
EN 61000-6-4
UL508
CSA-C22.2 No. 142-M
Model Code
XN-322-1CNT-8DIO

Toote tehnilised andmed

Used with
XN300
XN-312-…
Type
XN300 technology module
Features
Fieldbus connection over separate bus coupler possible
Flux controller possible
Fieldbus connection over separate bus coupler possible
Air discharge
8 kV/4 kV, Air/contact discharge, ESD
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
3
Connection
Push-in spring-cage terminal (plug-in connection) in TOP direction
Burst impulse
1 kV, Signal cable
2 kV, Supply cable
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Air pressure
795 - 1080 hPa (operation)
Explosion safety category for dust
None
Environmental conditions
Condensation: prevent with appropriate measures
Output voltage
< 1 V DC (Low level, digital outputs)
< 24 V DC (High level, digital outputs)
24 V DC (digital outputs)
Explosion safety category for gas
None
Output current
< 0.5 mA (low level)
2 A
≤ 2000 mA (high level, Digital outputs)
Mounting method
Rail mounting possible
Voltage type
DC
Mounting position
Horizontal
Number of channels
4
Safety performance level (EN ISO 13849-1)
None
SIL (IEC 61508)
None
Ambient operating temperature - max
60 °C
Ambient operating temperature - min
0 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-20 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Height of fall (IEC/EN 60068-2-32) - max
1 m
Number of functions
0
Number of HW-interfaces (industrial ethernet)
0
Number of HW-interfaces (other)
1
Number of HW-interfaces (parallel)
0
Number of HW-interfaces (RS-232)
0
Number of HW-interfaces (RS-422)
0
Number of HW-interfaces (RS-485)
0
Number of HW-interfaces (serial TTY)
0
Number of HW-interfaces (USB)
0
Number of HW-interfaces (wireless)
0
Number of interfaces (PROFINET)
0
Output
Protective devices must be installed directly at the inductive load in order to prevent interference.
Overvoltage category
III
Surge rating
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
1 kV, Signal cable, unbalanced, EMC
Emitted interference
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency)
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Load current
Not specified by plug manufacturer
Counter frequency
500 kHz max. (X4 encoding), Operating Mode TTL
500 kHz max. (X4 encoding), Operating Mode RS422
Radiated RFI
10 V
Load resistance
> 12 Ω
Current consumption
None mA (typ.), for +24 V, Power supply - Input
40 mA (typ.), for +5 V power supply (internal), Power supply - Input
Relative humidity
0 - 95 % (non-condensing)
Degree of protection
IP20
NEMA 1
Delay time
< 200 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal
< 200 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal
Protocol
Other bus systems
Rated control supply voltage
5 V (Sensor/transmitter supply)
Rated operational current (Ie)
6 A (supply input)
0.25 A (supply input)
Max. 0.2 A (supply output)
Suitable for
Incremental data detection
Counting
flux measurement
Functions
Single-axis positioning possible
X4 signal analysis
X1 signal analysis
Electronic positioning available
TTL Operating mode
X2 signal analysis
RS422 Operating mode
Frequency measurement
Single-axis controller possible
Gauge pin
A1 (according to IEC/EN 60947-1)
Vibration resistance
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
Incremental encoder
Heat dissipation (per active channel): 1.105 W
Must be wired using a screened cable. For RS422 encoders use a screened twisted-pair cable. Shielding must be terminated as close as possible to the module (upstream).
Channels: 1
Signals RS422: A, /A, B, /B, R, /R
Signals Bus termination resistor: 120 Ω (internal)
Signals TTL: A, B, R
Signals Bus termination resistor: 1200 Ω (internal pull-up resistor)
Input current
≥ 2.3 mA (Digital inputs, high level)
3.7 mA (Digital inputs)
≤ 1.1 mA (Digital inputs, low level)
Input delay
10 µs (falling edge)
10 µs (rising edge)
Shock resistance
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
Input frequency
125 kHz
Input voltage
0 - 8 V (Digital inputs, low level)
24 V DC (Digital inputs)
14 - 30 V (Digital inputs, high level)
Insulating material group
I
System accessory
Yes
Static heat dissipation, non-current-dependent Pvs
3.516 W
Stripping length (main cable)
10 mm
Supply voltage at DC - max
30 VDC
Supply voltage at DC - min
18 VDC
Product category
XN-322 counter module
Resolution
16 Bit (Functions)
Potential isolation
Between Digital inputs: no
Digital inputs, Input delay: no
Power supply, Input: no
Between Digital outputs: no
Sensor/transmitter supply: no
Voltage dips
Voltage dips: 10 ms/Voltage fluctuations: Yes
Rated operational voltage
160 V (terminations)
24 V (for incremental encoder)
24 V (for digital outputs)
Short-circuit protection
Yes, Short-circuit rating, Digital outputs
Terminal capacity
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
24 - 16 AWG
0.2 - 1.5 mm², flexible without ferrule, H07V-K
0.2 - 1.5 mm², solid, H07V-U
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)