Lae dokument alla () … 20
Tootmine lõpetatakse

290446
Mudeli kood: XC-CPU121-2C256K

Eaton XC Compact PLC, expandable, 24 V DC, RS232, RS485(RS232), 2xCAN

General specifications

Product Name
Eaton XC Modular PLC
Catalog Number
290446
EAN
4015082904463
Product Length/Depth
100 mm
Product Height
100 mm
Product Width
60 mm
Product Weight
0.195 kg
Certifications
CE
EN 50178
CSA Class No.: 2252-01
UL File No.: E135462
CSA
IEC/EN 61131-2
UL Category Control No.: NRAQ
CSA-C22.2 No. 0-M
UL
CSA File No.: 012528
CSA-C22.2 No. 142-M
UL508
EAC
Catalog Notes
can be locally expandable with I/O module XIO-EXT-121-1
Model Code
XC-CPU121-2C256K

Toote tehnilised andmed

Type
Modular PLC XC-CPU121
Features
Asynchronous, cyclic, acyclic PDO types (CAN1/CAN2 interface)
Expandable with XC-CPU121 expansions
Mains overvoltage protection (power supply)
Expandable with XI/OC expansions
Mains filter (power supply)
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
2
Air pressure
795 - 1080 hPa (operation)
Bus termination
Selectable for CAN1/CAN2, first and last station
External, for RS485
Explosion safety category for dust
None
Backup time
> 72 hours (time at zero voltage)
Explosion safety category for gas
None
Mounting method
Rail mounting possible
Wall mounting/direct mounting
Character formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1, Serial interface (RS232) without handshake lines, transparent mode
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1, COM2 (RS232/RS485) without handshake lines, transparent mode, set through function blocks
Voltage type
DC
Mounting position
Horizontal
Memory capacity
256 kByte
Number of channels
0
Safety performance level (EN ISO 13849-1)
None
SIL (IEC 61508)
None
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
0 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
-25 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Number of HW-interfaces (industrial ethernet)
0
Number of HW-interfaces (other)
1
Number of HW-interfaces (parallel)
0
Number of HW-interfaces (RS-232)
1
Number of HW-interfaces (RS-422)
0
Number of HW-interfaces (RS-485)
1
Number of HW-interfaces (USB)
0
Number of HW-interfaces (wireless)
0
Number of interfaces (PROFINET)
0
Number of outputs (analog)
0
Overvoltage category
II
Duty factor
100 %, Digital outputs
Supply voltage
20.4 - 28.8 V DC
Emitted interference
According to IEC/EN 61000-6-4
Terminal capacity (AWG)
28 - 20
Interference immunity
According to EN 61000-6-2
Protection against polarity reversal
Yes, for AS-Interface
Yes
Number of inputs (analog)
0
Connection type
Spring-loaded terminal block, 6-pole, COM2, CAN1, CAN2 interface
Spring-loaded terminal block
RJ45, Ethernet
Cycle time
< 0.3 ms, for 1 k of instructions (Bit, Byte), memory
Number of modules
126 (CAN1/CAN2 interface)
Memory type
RAM
Number of outputs (digital)
8
Data transfer rate
19.2 kBit/s, Serial interface (RS232) without handshake lines, Transparent mode
1.2 kBit/s, Serial interface (RS232) without handshake lines, Transparent mode
0.3 kBit/s, Serial interface (RS232) without handshake lines, Transparent mode
0.6 kBit/s, Serial interface (RS232) without handshake lines, Transparent mode
19.2 kBit/s, Serial interface (RS232) without handshake lines, Programming, Character format: 8 data bits, no parity, 1 stop bit
19.2 kBit/s, COM2 (RS232/RS485) without handshake lines, Transparent mode, Set through function blocks
10 - 500 kBit/s, CAN1/CAN2
1.2 kBit/s, COM2 (RS232/RS485) without handshake lines, Transparent mode, Set through function blocks
0.3 kBit/s, COM2 (RS232/RS485) without handshake lines, Transparent mode, Set through function blocks
0.6 kBit/s, COM2 (RS232/RS485) without handshake lines, Transparent mode, Set through function blocks
Relative humidity
10 - 95 % (non-condensing)
Degree of protection
IP20
Number of relay outputs
0
Protocol
PROFIBUS
SUCONET
MODBUS
CAN
Other bus systems
Residual ripple
≤ 5 %
Rapid counter inputs
190 bytes in each block
Rated operational current (Ie)
0 A
Inrush current
No limitation (limited only by upstream 24 V DC power supply unit)
Functions
Overvoltage protection
Additional program memory possible
Vibration resistance
5 - 9 Hz, Amplitude 3.5 mm
9 - 150 Hz, 1 g constant acceleration
Input current
60 mA
Processor
Infineon XC161
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Input voltage
24 V DC (Power supply)
24 V DC (Power supply of local inputs/outputs)
Number of time switches - max
1000
Processing time
0.5 ms
Rated insulation voltage (Ui)
500 V
Rated operational current for specified heat dissipation (In)
0 A
Repetition rate
1 s
Static heat dissipation, non-current-dependent Pvs
6 W
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 60 Hz - max
0 VAC
Supply voltage at AC, 60 Hz - min
0 VAC
Supply voltage at DC - max
28.8 VDC
Supply voltage at DC - min
20.4 VDC
Heat dissipation details
Without local I/O
Signal range
19.2 - 30 V DC (Power supply of local inputs/outputs, note polarity)
Memory
244 kByte Program data code, optional extension
4 kByte Input Memory
4 kByte Output Memory
8 kByte Retain Memory
16 kByte Marker Memory
256 kByte (User memory)
256 kByte Program memory code, optional extension
Interfaces
RS485/RS232 (built-in)
RS232 (built-in)
2 x CANopen® (built-in)
Number of bytes
190 bytes
System accessory
Yes
Model
Modular
Utilization factor
0 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH)
Potential isolation
CAN1/CAN2 interface: no
Power supply of local inputs/outputs (24 V/0 V) against CPU voltage: yes
Number of inputs (digital)
18
Power loss
6 W
Terminal capacity (solid/stranded)
0.14 - 1 mm²
Voltage dips
10 ms
Power consumption
Max 1.44 W
Terminal capacity
0.14 - 0.5 mm²
AWG 28-20
Terminal capacity (solid/stranded AWG)
28 - 18

Ekspordi toote tehnilised andmed