Eaton Moeller® series P1 On-Off switch, 40 A, flush mounting, 3 pole, with black thumb grip and front plate
Product Name |
Eaton Moeller® series P1 On-off switch
|
Catalog Number |
199889
|
EAN |
4015082953300
|
Product Length/Depth |
95 mm
|
Product Height |
70 mm
|
Product Width |
49 mm
|
Product Weight |
0.143 kg
|
Compliances |
UKCA
CE |
Certifications |
IEC/EN 60947
IEC/EN 60947-3 IEC/EN 60204 |
Catalog Notes |
Rated Short-time Withstand Current (Icw) for a time of 1 second
|
Model Code |
P1-40/E
|
Product Category |
On-Off switch
|
Actuator color |
Black
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Black thumb grip and front plate
Auxiliary contact |
Operating frequency |
50 Operations/h
|
Pollution degree |
3
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Rated permanent current at AC-21, 400 V |
40 A
|
Rated permanent current at AC-23, 400 V |
40 A
|
Rated uninterrupted current (Iu) |
40 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Switching angle |
90 °
|
Switching power at 400 V |
22 kW
|
Device construction |
Built-in device fixed built-in technique
|
Rated short-time withstand current (Icw) |
0.64 kA
640 A, Contacts, 1 second |
Electrical connection type of main circuit |
Screw connection
|
Mounting position |
As required
|
Actuator type |
Short thumb-grip
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
1.9 W
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Handle color |
Black
|
Rated conditional short-circuit current (Iq) |
80 kA
|
Overvoltage category |
III
|
Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
Degree of protection (front side) |
IP65
|
Number of poles |
3
|
Mounting method |
Flush mounting
|
Degree of protection |
IP65
|
Number of switches |
1
|
Safe isolation |
440 V AC, Between the contacts, According to EN 61140
|
Screw size |
M4, Terminal screw
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
|
Lifespan, mechanical |
300,000 Operations
|
Load rating |
1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor) 2 x Iₑ (with intermittent operation class 12, 25 % duty factor) |
Terminal capacity |
1 x (1 - 4) mm², flexible with ferrules to DIN 46228
2 x (1 - 4) mm², flexible with ferrules to DIN 46228 1 x 10 mm² with fork terminal 2 x 10 mm² with fork terminal |
Number of auxiliary contacts (normally open contacts) |
0
|
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) |
290 kA
|
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) |
130 kA
|
Rated operating voltage (Ue) - max |
690 V
|
Rated operating voltage (Ue) - min |
690 V
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Short-circuit protection rating |
50 A gG/gL, Fuse, Contacts
|
Rated operational current (Ie) at AC-21, 440 V |
40 A
|
Rated operational current (Ie) at AC-21, 500 V |
40 A
|
Rated operational current (Ie) at AC-21, 690 V |
40 A
|
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V |
40 A
|
Rated operational current (Ie) at AC-22, 500 V |
40 A
|
Rated operational current (Ie) at AC-22, 690 V |
40 A
|
Rated operational current (Ie) at AC-23A, 230 V |
40 A
|
Rated operational current (Ie) at AC-23A, 400 V, 415 V |
40 A
|
Rated operational current (Ie) at AC-23A, 690 V |
20 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
30 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
30 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
17 A
|
Rated operational current for specified heat dissipation (In) |
40 A
|
Rated operational power at AC-23A, 220/230 V, 50 Hz |
11 kW
|
Rated operational power at AC-23A, 400 V, 50 Hz |
22 kW
|
Rated operational power at AC-23A, 690 V, 50 Hz |
18.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
15 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
15 kW
|
Rated operational power at AC-3, 690 V, 50 Hz |
15 kW
|
Tightening torque |
1.6 Nm, Screw terminals
|
Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|