Unduh Dokumen () / 20
Kami membantu memastikan kebutuhan vital yang diperlukan oleh semua orang terpenuhi*

259610
Model code: NZM2/3-XUHIV220-250DC

Eaton Moeller series NZM Undervoltage release, 220-250VDC, +2early N/O, for NZM2/3

Spesifikasi umum

Product Name
Eaton Moeller series NZM Undervoltage release
Catalog Number
259610
Model Code
NZM2/3-XUHIV220-250DC
EAN
4015082596101
Product Length/Depth
42 mm
Product Height
90 mm
Product Width
30 mm
Product Weight
0.074 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
CSA (Class No. 1437-01)
CSA (File No. 22086)
IEC60947
CSA certified
UL (File No. E140305)
UL489
CE marking
CSA-C22.2 No. 5-09
UL (Category Control Number DIHS)
UL listed

Data teknis - elektrik

Voltage type
AC
Rated control voltage (relay contacts)
250 V DC
220 V DC
Rated control supply voltage
220 - 250 V DC
Rated control supply voltage (Us) at DC - min
220 V
Rated control supply voltage (Us) at DC - max
250 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
1.5 VA (sealing AC)
0.8 W (sealing DC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Data teknis - komunikasi

Rated control voltage (relay contacts)
250 V DC
220 V DC
Rated control supply voltage
220 - 250 V DC
Rated control supply voltage (Us) at DC - min
220 V
Rated control supply voltage (Us) at DC - max
250 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
1.5 VA (sealing AC)
0.8 W (sealing DC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Data teknis - mekanis

Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
2
Connection type
With bolt connection

dataSheetsExport