Model code: NZM2-4-XFIA

Eaton Moeller series NZM Earth-fault release, 0.3-1A AC/DC sensitive, 4p

Spesifikasi umum

Product Name
Eaton Moeller series NZM Earth leakage relay
Catalog Number
292346
Model Code
NZM2-4-XFIA
EAN
4015082923464
Product Length/Depth
132 mm
Product Height
103 mm
Product Width
140 mm
Product Weight
2.03 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2
IEC/EN 60947-2 annex B

Data teknis - elektrik

Sensitivity type
Sensitive to AC/DC (type B)
Voltage rating
50 - 400 V AC (independent of mains voltage)
Voltage rating at DC
50 V DC (dependent on mains voltage)
Rated operating voltage (Ue) - max
400 V
Rated control supply voltage (Us) at AC, 50 Hz - min
50 V
Rated control supply voltage (Us) at AC, 50 Hz - max
400 V
Rated control supply voltage (Us) at AC, 60 Hz - min
50 V
Rated control supply voltage (Us) at AC, 60 Hz - max
400 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
250 A
Rated fault current - min
0.3 A
Rated fault current - max
1 A
Fault current detection range
With AC voltage: 0 - 100 kHz
With pulsed DC voltage: 50 Hz
Frequency rating
50 Hz
Power on-delay time - min
100 ms
Power on-delay time - max
100 ms

Data teknis - komunikasi

Rated control supply voltage (Us) at AC, 50 Hz - min
50 V
Rated control supply voltage (Us) at AC, 50 Hz - max
400 V
Rated control supply voltage (Us) at AC, 60 Hz - min
50 V
Rated control supply voltage (Us) at AC, 60 Hz - max
400 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
250 A
Rated fault current - min
0.3 A
Rated fault current - max
1 A
Fault current detection range
With AC voltage: 0 - 100 kHz
With pulsed DC voltage: 50 Hz
Frequency rating
50 Hz
Power on-delay time - min
100 ms
Power on-delay time - max
100 ms

Data teknis - mekanis

Mounting Method
Bottom
Mounting position
Vertical and 90° in all directions
Degree of protection
IP20 (operating component area)
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Lifespan, mechanical
≧ 2000 operations