Eaton DA1 Frequency inverter, 230 V AC, 3-phase, 30 A, 7.5 kW, IP20/NEMA 0, Radio interference suppression filter, Brake chopper, Additional PCB protection, OLED display, FS4
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
197488
|
EAN |
4015081940639
|
Product Length/Depth |
241 mm
|
Product Height |
419 mm
|
Product Width |
173 mm
|
Product Weight |
9.2 kg
|
Certifications |
IEC/EN61800-3
Safety: EN 61800-5-1: 2003 UkrSEPRO UL Category Control No.: NMMS, NMMS7 CUL IEC/EN 61800-3 RCM RoHS, ISO 9001 UL UL 508C UL report applies to both US and Canada IEC/EN 61800-2 EAC IEC/EN61800-5 Certified by UL for use in Canada CE UL File No.: E172143 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Cable length |
100 m, screened, maximum permissible cable length
150 m, unscreened, maximum permissible cable length C3 ≤ 25 m, maximum motor cable length 200 m, unscreened, with motor choke, maximum permissible cable length C2 ≤ 5 m, maximum motor cable length 200 m, screened, with motor choke, maximum permissible cable length |
Communication interface |
EtherCAT, optional
SmartWire-DT, optional Modbus-TCP, optional Modbus RTU PROFIBUS, optional PROFINET, optional OP-Bus (RS485) CANopen® DeviceNet, optional Ethernet IP, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Fitted with: |
PC connection
Control unit Radio interference suppression filter IGBT inverter OLED display Additional PCB protection Internal DC link Breaking resistance Brake chopper |
Frame size |
FS4
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
CAN
Other bus systems TCP/IP MODBUS PROFIBUS PROFINET IO EtherNet/IP DeviceNet |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
Ambient operating temperature - min |
-10 °C
|
Altitude |
Max. 1000 m
Above 1000 m with 1 % derating per 100 m Max. 4000 m |
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
96.1 % (η)
|
Heat dissipation at current/speed |
127 W at 25% current and 0% speed
130 W at 25% current and 50% speed 160 W at 50% current and 0% speed 171 W at 50% current and 50% speed 214 W at 50% current and 90% speed 284 W at 100% current and 0% speed 337 W at 100% current and 50% speed 410 W at 100% current and 90% speed |
Input current ILN at 150% overload |
36.4 A
|
Leakage current at ground IPE - max |
1.42 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
Speed control with slip compensation
Sensorless vector control (SLV) U/f control Optional: Vector control with feedback (CLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Overload current IL at 150% overload |
45 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
30 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
7.5 kW
|
Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
50 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 VAC
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
28 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
30 A
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
10 HP
|
Apparent power at 230 V |
11.95 kVA
|
Apparent power at 240 V |
12.47 kVA
|
Braking resistance |
22 Ω
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 100 % (DC) |
Switch-on threshold for the braking transistor |
390 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|