Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 3.3 A, 1.1 kW, IP54/NEMA12, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9702-1103-00P
|
EAN |
4015081710782
|
Product Length/Depth |
200.9 mm
|
Product Height |
327 mm
|
Product Width |
153 mm
|
Product Weight |
6.7 kg
|
Certifications |
IEC/EN 61800-3
UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 CE Certified by UL for use in Canada EAC UL UL508 CUL IEC/EN61800-5 UL report applies to both US and Canada Safety requirements: IEC/EN 61800-5 IEC/EN61800-3 Specification for general requirements: IEC/EN 61800-2 CSA-C22.2 No. 274-13 UkrSEPRO C-Tick RoHS, ISO 9001 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Tool-less swapping of fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Additional PCB protection
Radio interference suppression filter Brake chopper DC link choke Internal DC link Multi-line graphic display Control unit PC connection Breaking resistance IGBT inverter |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Operating mode |
Torque regulation
Speed control with slip compensation U/f control Sensorless vector control (SLV) |
Frame size |
FS1
|
Air volume capacity |
24 m³/h
|
Altitude |
Max. 2000 m for Corner Grounded TN Systems
Max. 1000 m Above 1000 m with 1 % derating per 100 m Max. 3000 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
3 kVA
|
Apparent power at 480 V |
3.7 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
3.6 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
2.6 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
2.2 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
17.33 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
BACnet MS/TP, built in
Modbus TCP, built in DeviceNet, optional SmartWire-DT, optional Modbus RTU, built in CANopen®, optional Ethernet IP, built in PROFIBUS, optional |
Converter type |
U converter
|
Degree of protection |
NEMA 12
IP54 |
Protocol |
MODBUS
PROFIBUS DeviceNet PROFINET IO CAN Other bus systems TCP/IP BACnet EtherNet/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
3 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
3.4 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
4 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
2.9 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
1.5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload |
2 HP
|
Braking resistance |
63 Ω
|
Equipment heat dissipation, current-dependent Pvid |
73 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
4 A
|
Input current ILN at 150% overload |
3.1 A
|
Mains current distortion |
35.3 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Adjustable to 150 %, DC - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
C3 ≤ 50 m, Radio interference level, maximum motor cable length 100 m, screened, maximum permissible, Motor feeder |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
73 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
98.1 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
2.9 mA
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
3.3 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
1.1 kW
|
Output at quadratic load at rated output voltage - max |
1.5 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
4.73 A
|
Overload current IL at 150% overload |
4.95 A
|
Shock resistance |
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 UPS drop test (for weights inside the UPS frame) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
4.3 A
|
Rated operational current (Ie) at 150% overload |
3.3 A
|
Rated operational current for specified heat dissipation (In) |
3.3 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.1 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload |
1.5 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
1.5 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
28 W at 25% current and 0% speed
29 W at 100% current and 50% speed 37 W at 100% current and 0% speed 38 W at 25% current and 50% speed 43 W at 50% current and 50% speed 47 W at 50% current and 90% speed 54 W at 50% current and 0% speed 60 W at 100% current and 90% speed |