Eaton DG1 Variable frequency drive, 500 V AC, 3-phase, 62 A, 37 kW, IP21/NEMA1, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9703-4012-00P
|
EAN |
4015081772377
|
Product Length/Depth |
294 mm
|
Product Height |
630 mm
|
Product Width |
237.7 mm
|
Product Weight |
34.1 kg
|
Certifications |
Safety requirements: IEC/EN 61800-5
IEC/EN61800-5 Specification for general requirements: IEC/EN 61800-2 UL File No.: E134360 UkrSEPRO UL508 RoHS, ISO 9001 C-Tick Certified by UL for use in Canada CSA-C22.2 No. 274-13 UL report applies to both US and Canada UL CUL IEC/EN 61800-3 UL Category Control No.: NMMS, NMMS7 CE EAC IEC/EN61800-3 |
Features |
Externally accessible fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Air volume capacity |
260 m³/h
|
Cable length |
200 m, screened, maximum permissible, Motor feeder
C3 ≤ 10 m, Radio interference level, maximum motor cable length |
Degree of protection |
NEMA 1
IP21 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
Multi-line graphic display
Control unit IGBT inverter Radio interference suppression filter PC connection DC link choke Internal DC link Additional PCB protection |
Frame size |
FS4
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Altitude |
Max. 2000 m
Above 1000 m with 1 % derating per 100 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
98.3 % (η)
|
Heat dissipation at current/speed |
308 W at 25% current and 0% speed
358 W at 25% current and 50% speed 408 W at 100% current and 50% speed 494 W at 50% current and 50% speed 534 W at 50% current and 90% speed 723 W at 100% current and 0% speed 868 W at 50% current and 0% speed 998 W at 100% current and 90% speed |
Input current ILN at 110% overload |
73 A
|
Input current ILN at 150% overload |
57.6 A
|
Leakage current at ground IPE - max |
6 mA
|
Mains current distortion |
31.2 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
525 V
|
Mains voltage - max |
600 V
|
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) Torque regulation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
600 V AC, 3-phase
|
Overload current IL at 110% overload |
88 A
|
Overload current IL at 150% overload |
93 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
80 A
|
Rated operational current (Ie) at 150% overload |
62 A
|
Rated operational voltage |
600 V AC, 3-phase
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
125 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 525 V, 50 Hz, 110% overload |
79 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
54 A
|
Assigned motor current IM at 600 V, 50 Hz, 110% overload |
68.9 A
|
Assigned motor current IM at 600 V, 50 Hz, 150% overload |
57.1 A
|
Apparent power at 600 V |
83.1 kVA
|
Braking resistance |
9 Ω
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
1050 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
BACnet MS/TP, built in
DeviceNet, optional Ethernet IP, built in PROFIBUS, optional Modbus RTU, built in Modbus TCP, built in SmartWire-DT, optional CANopen®, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Protocol |
Other bus systems
TCP/IP PROFIBUS DeviceNet CAN MODBUS PROFINET IO BACnet EtherNet/IP |
Equipment heat dissipation, current-dependent Pvid |
1187 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
62 A
|
Static heat dissipation, non-current-dependent Pvs |
24.65 W
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|