Télécharger le document () de 20
Nous agissons afin que ce qui compte fonctionne*

101560
Model Code: BC-A-3/39-TW

BC-A-3/39-TW . Surface-mount DBO, 3-row, with rear wall and white door, class 2

Spécifications générales

Product Name
Eaton xComfort BC version A
Catalog Number
101560
EAN
4015081014521
Product Length/Depth
480 mm
Product Height
145 mm
Product Width
260 mm
Product Weight
1.8 kg
Compliances
RoHS conform
Model Code
BC-A-3/39-TW

Delivery program

Color
White

Technical data - mechanical

Closure type
Other
Enclosure material
Plastic
Width in number of modular spacings
13
Mounting method
DIN-rail
Surface mounted (plaster)
Degree of protection
IP40
Number of rows
3
Built-in depth
46 mm
Built-in height
0 mm
Built-in width
234 mm
Internal depth
72 mm
Cover/door model
With notch
Cover/door type
Door
Single

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
20 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
41 W

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
650 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK07
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP40
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Functions
Sealable
RAL-number
9010

Exporter les spécifications du produit

Declarations of conformity

Remarque : L’absence d’un ou plusieurs fichiers dans un ficher .zip téléchargé peut être causée par l’absence de prise en charge du type de fichier pour un téléchargement groupé.