197211
EASY-E4-UC-12RC1

Eaton Moeller® series EASY Control relays easyE4 with display (expandable, Ethernet), 12/24 V DC, 24 V AC, Inputs Digital: 8, of which can be used as analog: 4, screw terminal

General specifications

Product Name
Eaton Moeller® series EASY Control relay
Catalog Number
197211
EAN
4015081939480
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
72 mm
Product Weight
0.25 kg
Compliances
Eaton supports the product until its end of life
Certifications
UL File No.: E205091
CE
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location class I
UL hazardous location group D (propane)
cULus Ordinary Location
DNV
TAA00002HT
cULus Hazard Location
UL File No.: E523283
EN 61131-2
IEC 61131-2
EN IEC 61000-6-3
IEC 61000-6-3
EN IEC 61010-2-201
IEC 61010-2-201
UL 61010-1
UL 61010-2-201
CSA C22.2 No. 61010-1
CSA C22.2 No. 61010-2-201
UL 121201
CSA C22.2 No. 213
Catalog Notes
Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible

Features & Functions

Features
Expandable
Display indication of 6 lines x 16 characters
Networkable (Ethernet)
Fitted with:
Display
Real time clock
Relay output
Keypad
Timer
Indication
LCD-display used as status indication of digital I/Os

General

Degree of protection
IP20
Display temperature - min
0 °C
Display temperature - max
55 °C
Display type
Monochrome
Duty factor
100 %
Frequency counter
Cable length: ≤ 20 m (shielded)
Counter frequency: ≤ 5 kHz
Number: 4 (I1, I2, I3, I4)
Pulse pause ratio: 1:1
Pulse shape: Square
Input frequency
50/60 Hz (Digital inputs at AC)
Insulation resistance
According to EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-211
Lifespan, electrical
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
Lifespan, mechanical
10,000,000 Operations
Mounting method
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Overvoltage category
Power supply + Inputs + Extension: II
Relay outputs: III
Pollution degree
2
Product category
Control relays easyE4
Protection
B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay
Protocol
Modbus TCP
Rated impulse withstand voltage (Uimp)
Relay outputs: 6 kV (contact-coil)
Residual ripple
Power supply: ≤ 5 %
Resolution
12 Bit (value 0 - 4095, Analog inputs)
Software
EASYSOFT-SWLIC/easySoft
Switching frequency
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs
0.5 Hz, Inductive load, Relay outputs
Type
easyE4 base device
Used with
easyE4
Utilization category
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Voltage type
AC/DC

Ambient conditions, mechanical

Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Vertical
Horizontal
Shock resistance
15 g, Mechanical, acc. to IEC/EN61131-2, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
8.4 - 150 Hz, 1 g constant acceleration
5 - 8.4 Hz, 3.5 mm constant amplitude
According to IEC/EN 61131-2

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)

Electro magnetic compatibility

Air discharge
8 kV
Burst impulse
2 kV, I/O port
2 kV, Power supply port
1 kV, communication port
According to IEC/EN 61131-2
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC/EN 61131-2)
3 V/m at 1.0 - 6 GHz (according to IEC/EN 61131-2)
Immunity to line-conducted interference
10 V (according to IEC/EN 61131-2)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
1 kV, Line-to-Line, Power supply port
2 kV, Line-to-Earth, Power supply port
1 kV, Line-to-Line, Input port
2 kV, Line-to-Earth, Input port
1 kV, Line-to-Earth, communication port
According to IEC/EN 61131-2
Voltage dips
1 ms 12 V DC
10 ms at 24 V DC
20 ms at 24 V AC

Terminal capacities

Terminal capacity
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm², flexible with ferrule
0.2 - 2.5 mm², flexible without ferrule
Screwdriver size
3.5 x 0.6 mm, Terminal screw
Tightening torque
0.6 Nm, Screw terminals

Electrical rating

Power consumption
3 W
Power loss
10 VA
Rated breaking capacity
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 Ops./h)
Rated operational voltage
Power supply: 24 V DC (-15 %/+ 20 %)
Power supply: 24 V AC (-15 %/+ 10 %)
Power supply: 12 V DC (-15 %/+ 20 %)
Relay outputs: max. 300 V AC/DC
Inputs: shall be identical to the power supply voltage
Supply frequency
50/60 Hz (± 5%)
Supply voltage at AC, 50 Hz - min
20.4 VAC
Supply voltage at AC, 50 Hz - max
26.4 VAC
Supply voltage at DC - min
10.2 VDC
Supply voltage at DC - max
28.8 VDC
Uninterrupted current
1 A DC, at R 300 (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA)

Short-circuit rating

Short-circuit protection
≥ 1A (T), Fuse, Power supply

Communication

Connection type
Screw terminal
Ethernet: RJ45 plug, 8-pole
Data transfer rate
10/100 MBit/s

Cable

Cable length
Digital inputs (DC): ≤ 100 m (unshielded)
Digital inputs (AC): ≤ 40 m (unshielded)
Analog inputs: ≤ 30 m (shielded)
Cable type
Ethernet: CAT5

Input/Output

Accuracy
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)
± 2 %, (I5, I6, I7, I8) ± 0.12 V, of actual value, within a single device (Analog Inputs)
± 1 %, Repetition accuracy of timing relays (of values)
± 3 %, of actual value, two easy devices (Analog Inputs)
Conversions
Each CPU cycle for Analog inputs
Delay time
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
Incremental counter
Number of counter inputs: 2 (I1 + I2, I3 + I4)
Value range: -2147483648 to +2147483647
Pulse shape: Square
Pulse pause ratio: 1:1
Signal offset: 90°
Counter frequency: ≤ 5 kHz
Cable length: ≤ 20 m (shielded)
Input
Voltage (DC)
Input current
1.8 mA (I5 - I8, at 24 V DC,at signal 1)
3.3 mA (I1 - I4, at 24 V DC,at signal 1)
3.5 mA (I1 - I4, at 24 V AC,at signal 1)
1.8 mA (I5 - I8, at 24 V AC,at signal 1)
0.9 mA (I5 - I8, at 12 V DC,at signal 1)
1.75 mA (I1 - I4, at 12 V DC,at signal 1)
< 1 mA (Analog inputs)
Input impedance
Analog: 13.3 kΩ
Input voltage
Condition 0: ≤ 5 V DC (Digital inputs, 12 V DC)
Condition 0: ≤ 5 V DC (Digital inputs, 24 V DC)
Condition 1: ≥ 15 V DC (Digital inputs, 24 V DC)
Condition 1: ≥ 8 V DC (Digital inputs, 12 V DC)
Condition 0: ≤ 5 V AC (Digital inputs, 24 V AC)
Condition 1: ≥ 15 V AC (Digital inputs, 24 V AC)
Making/breaking capacity
28/28 VA (DC, at R 300)
3600/360 VA (AC, at B 300)
Number of inputs (analog)
0
4
Number of inputs (digital)
4
8
Number of outputs (analog)
0
Number of outputs (digital)
4
Output
4 Relay Outputs
min. recommended load: 12 V AC/DC > 500 mA
Parallel switching
Not permitted
Rapid counter inputs
Counter frequency: ≤ 10 kHz
Value range: -2147483648 to +2147483647
Cable length: ≤ 20 m (shielded)
Pulse pause ratio: 1:1
Pulse shape: Square
Number of rapid counter inputs: 4 (I1, I2, I3, I4)
Signal range
0 - 10 V DC, Analog inputs

Safety

Explosion safety category for gas
None
Potential isolation
Power supply + Inputs + Extension interface against Outputs: yes
POW+Inputs+Extension interface vs. Ethernet+Functional Earth: yes
Outputs against Ethernet + Functional Earth: yes
Outputs against each other: yes
Protection against polarity reversal
Yes
Explosion safety category for dust
None
Safe isolation
Relay outputs: 300 V AC, Between two contacts
Relay outputs: 300 V AC, Between coil and contact

Design verification

Equipment heat dissipation, current-dependent Pvid
1 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Static heat dissipation, non-current-dependent Pvs
3 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification

eCAD model

Product notifications

Software, firmware, and applications

Note: If file(s) are missing from the .zip download then the file type is not supported by bulk download.
Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Authenticate Product

Enter your 16-17 digit serial number
The serial number you entered should not contain special charachter. The serial number you entered is not correct it should be of 16 or 17 digit. The serial number you entered was not found. Please try again or report this issue for further assistance. The serial number you entered does not match the product. Check your product's serial number and try again. Click here to navigate to the product page for the serial number you have entered The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance.
Serial number
Reset The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance. The Serial Number is not recognised by Eaton and is invalid. Please use this form to report this issue for further assistance.
Enter the 6 digit authentication code
The product you entered is suspect! Please try again or report this issue for further assistance. The authentication code you enter does not match our records for this serial number. Please try again, or report this issue for further assistance. Invalid Authentication code. Length must be 6 characters report this issue for further assistance. Authentication code is required report this issue for further assistance.
Complete Captcha challenge before authenticating.
Contact us to report-issue
x
Report an Issue
Please enter your full name.
x
Thank you, your issue has been submitted, our product team will contact with you soon.

Register Product

Please complete the form to register your product