Eaton's Cooper Power series VFI vacuum fault interrupter switchgear provides an environmentally preferred, safer and more reliable approach to medium-voltage switching and protection. Additionally, it features dead-front construction and enhanced operating features for added safety, all completely immersed within a sealed, insulated medium.
15 kV | 15 kV | 25 kV | 35 kV | ||
Maximum design voltage, kV | 15.5 | 15.5 | 27.0 | 38.0 | |
BIL, kV | 95 | 95 | 125 | 150 | |
1-minute withstand voltage (60 Hz), kV | 35 | 35 | 60 | 70 | |
Momentary current, 10 cycles (sym.), kA | 12.5 | 16.0 | 12.5 | 12.5 | |
1-second withstand current (sym.), kA | 12.5 | 16.0 | 12.5 | 12.5 | |
Vacuum fault interrupter | Continuous current, (max.), A | 600** | 600 | 600** | 600 |
Interrupting current (sym./asym.), kA | 12.5/20.0 | 16/25.8 | 12.5/20.0 | 12.5/20.0 | |
Making current (sym.), kA | 12.5 | 16.0 | 12.5 | 12.5 | |
Cable charging interrupting current, A | 10.0 | 10.0 | 25.0 | 40.0 | |
Load-break switch | Continuous current, (max), A | 600 | 600 | 600 | 600 |
Load switching, A | 600 | 600 | 600 | 600 | |
Fault making (sym./asym.), kA | 12.5/20.0 | 16/25.8 | 12.5/20.0 | 12.5/20 | |
* Continuous and short-circuit currents may be limited by ratings of selected bushings | |||||
** 900 A and 1200 A continuous-current ratings are also available |