Eaton Moeller® series Rapid Link - DOL starter, 6.6 A, Sensor input 4, Actuator output 2, PROFINET, HAN Q4/2, with manual override switch
Product Name |
Eaton Rapid Link DOL starter
|
Catalog Number |
199129
|
EAN |
4015081971879
|
Product Length/Depth |
120 mm
|
Product Height |
270 mm
|
Product Width |
220 mm
|
Product Weight |
1.83 kg
|
Certifications |
CCC
IEC/EN 60947-4-2 UL approval RoHS CE UL 60947-4-2 UL 60947-4-2 |
Catalog Notes |
Assigned motor rating: for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm at 50 Hz or 1800 min at 60 Hz
|
Features |
Parameterization: Fieldbus
Parameterization: Keypad Parameterization: drivesConnect mobile (App) Parameterization: drivesConnect |
Fitted with: |
Key switch position OFF/RESET
Key switch position HAND 2 Actuator outputs Thermistor monitoring PTC Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation Electronic motor protection Key switch position AUTO Manual override switch Thermo-click Short-circuit release |
Functions |
External reset possible
Temperature compensated overload protection |
Class |
CLASS 10 A
|
Degree of protection |
IP65
NEMA 12 |
Electromagnetic compatibility |
Class A
|
Lifespan, electrical |
10,000,000 Operations (at AC-3)
|
Lifespan, mechanical |
10,000,000 Operations (at AC-3)
|
Model |
Direct starter
|
Overload release current setting - min |
0.3 A
|
Overload release current setting - max |
6.6 A
|
Overvoltage category |
III
|
Product category |
Motor starter
|
Protocol |
PROFINET IO
|
Rated impulse withstand voltage (Uimp) |
4000 V
|
System configuration type |
AC voltage
Center-point earthed star network (TN-S network) Phase-earthed AC supply systems are not permitted. |
Type |
DOL starter
|
Voltage type |
DC
|
Mounting position |
Vertical
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft
|
Vibration |
Resistance: 10 - 150 Hz, Oscillation frequency
Resistance: 57 Hz, Amplitude transition frequency on acceleration Resistance: 6 Hz, Amplitude 0.15 mm Resistance: According to IEC/EN 60068-2-6 |
Altitude |
Max. 1000 m
Max. 2000 m Above 1000 m with 1 % performance reduction per 100 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
In accordance with IEC/EN 50178
< 95 %, no condensation |
Current limitation |
Adjustable, motor, main circuit
0.3 - 6.6 A, motor, main circuit |
Input current |
6.6 A (at 150 % Overload)
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage tolerance |
380 - 480 V (-15 %/+10 %, at 50/60 Hz)
|
Off-delay |
20 - 35 ms
|
On-delay |
20 - 35 ms
|
Output frequency |
50/60 Hz
|
Overload cycle |
AC-53a
|
Rated frequency - min |
47 Hz
|
Rated frequency - max |
63 Hz
|
Rated operational current (Ie) |
6.6 A
|
Rated operational current (Ie) at 150% overload |
6.6 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
6.6 A
|
Rated operational power at 380/400 V, 50 Hz - min |
0.09 kW
|
Rated operational power at 380/400 V, 50 Hz - max |
3 kW
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
0 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
3 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Supply frequency |
50/60 Hz, fLN, Main circuit
|
System configuration type |
AC voltage
Center-point earthed star network (TN-S network) Phase-earthed AC supply systems are not permitted. |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
3 HP
|
Rated conditional short-circuit current (Iq) |
10 kA
|
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
0 A
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Rated control voltage (Uc) |
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
|
Connection |
Connections pluggable in power section
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
2
|
Cable length |
10 m, Radio interference level, maximum motor cable length
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|