Photo is representative
Download
Eaton Moeller® series MSC-DE DOL starter, Ir= 3 - 12 A, 220 V 50 Hz, 240 V 60 Hz, AC voltage
| Product Name |
Eaton Moeller® series MSC-DE DOL starter
|
| Catalog Number |
167808
|
| EAN |
4015081643875
|
| Product Length/Depth |
145 mm
|
| Product Height |
272 mm
|
| Product Width |
45 mm
|
| Product Weight |
1.174 kg
|
| Certifications |
CSA-C22.2 No. 14-10
UL Category Control No.: NKJH VDE 0660 UL File No.: E123500 IEC/EN 60947-4-1 UL60947-4-1A CSA CE CSA Class No.: 3211-08 CSA File No.: 012528 UL |
| Model Code |
MSC-DE-12-M17-SP(220V50HZ,240V60HZ)
|
| Fitted with: |
Short-circuit release
|
| Functions |
Temperature compensated overload protection
|
| Class |
Adjustable
|
| Connection |
Screw terminals
|
| Connection to SmartWire-DT |
No
|
| Current flow times - min |
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
Note: Going below the minimum current flow time can cause overheating of the load (motor). 500 (Class 5) AC-4 cycle operation, Main conducting paths 900 (Class 15) AC-4 cycle operation, Main conducting paths 1000 (Class 20) AC-4 cycle operation, Main conducting paths 700 (Class 10) AC-4 cycle operation, Main conducting paths |
| Cut-out periods - min |
≤ 500 ms, main conducting paths, AC-4 cycle operation
|
| Degree of protection |
IP20
NEMA Other |
| Model |
UL Type E starter
|
| Mounting method |
DIN rail
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
1
|
| Overload release current setting - min |
3 A
|
| Overload release current setting - max |
12 A
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Type |
Starter with electronic trip unit
|
| Voltage type |
AC
|
| Altitude |
Max. 2000 m
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Rated operational current (Ie) |
16.7 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
12 A
|
| Rated operational power at AC-3, 220/230 V, 50 Hz |
3 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
7.5 kW
|
| Rated operational voltage |
208 - 600 V AC
|
| Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
| Short-circuit current rating (basic rating) |
60 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA) 60 A, max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) |
100 kA, Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA) 25 A, max. CB, SCCR (UL/CSA) 35 A, Class J/CC, max. Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) |
100 kA, Fuse, SCCR (UL/CSA)
35 A, Class J/CC, max. Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (type E) |
18 kA, 480 Y/277 V, SCCR (UL/CSA)
18 kA, 240 V, SCCR (UL/CSA) |
| Short-circuit release (Irm) - max |
186 A
|
| Power consumption, sealing, 50 Hz |
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
220 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
220 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
240 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
3 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 3-phase |
3 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
7.5 HP
|
| Equipment heat dissipation, current-dependent Pvid |
4.2 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
1.4 W
|
| Rated operational current for specified heat dissipation (In) |
12 A
|
| Static heat dissipation, non-current-dependent Pvs |
2.1 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|