Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 9.5 A, 4 kW, IP66/NEMA 4X, Radio interference suppression filter, Brake chopper, FS2 DC1-349D5FB-A66CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185756
|
EAN |
4015081812554
|
Product Length/Depth |
192 mm
|
Product Height |
257 mm
|
Product Width |
188 mm
|
Product Weight |
5 kg
|
Certifications |
Certified by UL for use in Canada
IEC/EN61800-3 EAC RoHS, ISO 9001 UL CE CSA-C22.2 No. 14 RCM UkrSEPRO UL File No.: E172143 Specification for general requirements: IEC/EN 61800-2 UL report applies to both US and Canada CUL IEC/EN 61800-3 UL Category Control No.: NMMS, NMMS7 Safety requirements: IEC/EN 61800-5-1 UL 508C IEC/EN61800-5 |
Catalog Notes |
Environmental class: 3C3, 3S3
|
Model Code |
DC1-349D5FB-A66CE1
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
Internal DC link
Breaking resistance Control unit IGBT inverter 7-digital display assembly Radio interference suppression filter Brake chopper PC connection Additional PCB protection |
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
100 m, screened, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, Radio interference level, maximum motor cable length C2 ≤ 5 m, Radio interference level, maximum motor cable length 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
CANopen®, built in
Modbus RTU, built in OP-Bus (RS485), built in SmartWire-DT, optional |
Connection to SmartWire-DT |
No
|
Degree of protection |
NEMA 4X
IP66 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS2
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
MODBUS
Other bus systems CAN EtherNet/IP |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
96.6 % (η)
|
Input current ILN at 150% overload |
11.5 A
|
Leakage current at ground IPE - max |
12.6 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) BLDC motors PM motors Synchronous reluctance motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
60 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Overload current IL at 150% overload |
14.25 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
At a switching frequency of 16 kHz and an ambient air temperature of +40 °C
9.5 A at 150% overload |
Rated operational power at 380/400 V, 50 Hz, 3-phase |
4 kW
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
50/60 Hz, fLN, Main circuit |
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 V
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
8.5 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
7.6 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
Apparent power at 400 V |
6.58 kVA
|
Apparent power at 480 V |
7.9 kVA
|
Braking resistance |
120 Ω
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
780 VDC
|
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
2 |
Number of inputs (digital) |
4 (parameterizable, max. 30 V DC)
4 |
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
1 (parameterizable, 24 V DC) |
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Equipment heat dissipation, current-dependent Pvid |
136 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
9.5 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Heat dissipation details |
Operation (with 150 % overload)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|