Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 2.2 A, 0.75 kW, IP66/NEMA 4X, Radio interference suppression filter, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199430
|
EAN |
4015081978199
|
Product Length/Depth |
162 mm
|
Product Height |
232 mm
|
Product Width |
161 mm
|
Product Weight |
2.5 kg
|
Certifications |
UL report applies to both US and Canada
UkrSEPRO UL CE RCM IEC/EN61800-5 UL Category Control No.: NMMS, NMMS7 EAC Certified by UL for use in Canada CSA-C22.2 No. 14 CE marking RoHS, ISO 9001 IEC/EN 61800-2 UL File No.: E172143 IEC/EN 61800-3 IEC/EN 61800-5-1 CUL UL 508C UL Listed |
Catalog Notes |
|
Model Code |
DC1-342D2FN-A6SOE1
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Keypad Parameterization: Fieldbus |
Fitted with: |
PC connection
UV resistance Internal DC link Local controls 7-digital display assembly Radio interference suppression filter Control unit Additional PCB protection IGBT inverter |
Cable length |
50 m, screened, maximum permissible, Motor feeder
C2 ≤ 5 m, maximum motor cable length 75 m, unscreened, maximum permissible, Motor feeder 100 m, screened, with motor choke, maximum permissible, Motor feeder 150 m, unscreened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, maximum motor cable length |
Communication interface |
CANopen®, built in
OP-Bus (RS485), built in SmartWire-DT, optional Modbus RTU, built in |
Connection to SmartWire-DT |
No
|
Degree of protection |
NEMA 4X
IP66 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS1
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
MODBUS
CAN Other bus systems EtherNet/IP |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Input current ILN at 150% overload |
3.5 A
|
Leakage current at ground IPE - max |
13 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
Sensorless vector control (SLV)
Speed control with slip compensation U/f control Synchronous reluctance motors PM motors BLDC motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Overload current IL at 150% overload |
3.3 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
2.2 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.5 kW
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
6 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 % IH
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 V
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
1.9 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
2.1 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
1 HP
|
Apparent power at 400 V |
1.52 kVA
|
Apparent power at 480 V |
1.83 kVA
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|