Eaton xEffect - XNH circuit protection. NH fuse-switch 3p box terminal 95 - 300 mm², busbar 60 mm, electronic fuse monitoring, NH2
| Product Name | 
                                                Eaton xEffect XNH device for busbar system
                                             | 
| Catalog Number | 
                                                183070
                                             | 
| Model Code | 
                                                XNH2-FCE-S400-BT
                                             | 
| EAN | 
                                                4015081779970
                                             | 
| Product Length/Depth | 
                                                306 mm
                                             | 
| Product Height | 
                                                190 mm
                                             | 
| Product Width | 
                                                210 mm
                                             | 
| Product Weight | 
                                                4.099 kg
                                             | 
| Compliances | 
                                                RoHS conform
                                             | 
| Certifications | 
                                                IEC/EN 60947-3
                                             | 
| Features | 
                                                Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-5  Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4 Halogen free Standard sealable | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Ui = 800 V AC
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| Fitted with: | 
                                                Connectors  Error protection | 
| Frequency rating | 
                                                40 Hz - 60 Hz
                                             | 
| Pollution degree | 
                                                3
                                             | 
| Creepage resistance | 
                                                CTI 600
                                             | 
| Equipment heat dissipation, current-dependent | 
                                                22 W
                                             | 
| Rated uninterrupted current (Iu) | 
                                                400 A
                                             | 
| Switching current of electronic fuse monitoring - max | 
                                                1 A
                                             | 
| Total heat dissipation without fuses at Ith | 
                                                36 W
                                             | 
| Voltage rating at AC - max | 
                                                250 VAC
                                             | 
| Voltage rating at DC - max | 
                                                24 VDC
                                             | 
| Ambient operating temperature details | 
 | 
| Voltage rating at AC | 
 | 
| Voltage rating at DC | 
                                                440 V (DC-22B)
                                             | 
| Conditioned rated short-circuit current Iq | 
                                                120 kA
                                             | 
| Number of poles | 
                                                Three-pole
                                             | 
| Rated operation power at AC-23, 400 V | 
                                                0 kW
                                             | 
| Size | 
                                                NH2 fuse
                                             | 
| Rated impulse withstand voltage (Uimp) | 
                                                8 kV
                                             | 
| Color | 
                                                Gray
                                             | 
| Connection type | 
                                                Box terminal
                                             | 
| Degree of protection | 
                                                IP2XC (contact protection, XNH installed)  IP10 (handle cover open, XNH installed) IP3X IP20 (operating status, XNH installed) | 
| Rated short-time withstand current (Icw) | 
                                                3 kA
                                             | 
| Direction of incoming supply | 
                                                As required (FLEX System)
                                             | 
| Electrical connection type of main circuit | 
                                                Frame clamp
                                             | 
| Activation type | 
                                                Dependent manual activation
                                             | 
| Actuator position | 
                                                Front side
                                             | 
| Actuator type | 
                                                Cover grip
                                             | 
| Voltage inputs | 
                                                400 V AC - 500 V AC (+/-10%)
                                             | 
| Voltage test | 
                                                Yes, sliding inspection windows
                                             | 
| Heat dissipation at 80% without fuses | 
                                                22.9 W
                                             | 
| Heat dissipation per pole, current-dependent | 
                                                7.3 W
                                             | 
| Mounting position | 
                                                Vertical or horizontal
                                             | 
| Suitable for | 
                                                Busbar mounting  Front mounting | 
| Rated conditional short-circuit current (Iq) | 
                                                120 kA
                                             | 
| Overvoltage category | 
                                                III (230/400 V)  III II (500 V) | 
| Suitable for fuses | 
                                                NH2
                                             | 
| Material | 
                                                Polyamide
                                             | 
| Cable entry type | 
                                                Other
                                             | 
| Frequency rating of contacts | 
                                                40 Hz - 60 Hz
                                             | 
| Mounting method | 
                                                Busbars of 60 mm
                                             | 
| Rated operation current (Ie) | 
                                                400 A
                                             | 
| Locking facility | 
                                                Yes, optional
                                             | 
| Flammability characteristics (UL) | 
                                                Self-extinguishing (UL 94)
                                             | 
| Type | 
                                                Fuse control - electronic
                                             | 
| Special features | 
 | 
| Degree of protection (front side) | 
                                                Other
                                             | 
| Heat deflection temperature | 
                                                125 °C
                                             | 
| Lifespan, electrical | 
                                                200 operations
                                             | 
| Lifespan, mechanical | 
                                                800 operations
                                             | 
| Electronic fuse monitoring | 
                                                1 NC  1 NO > 1 kOhm/V 3 LEDs (F1, F2, F3) red 1.5 VA Test button for relay + LEDs NH with live handle straps Self-supplied 1 LED green | 
| Terminal capacity (copper busbar) | 
                                                Max. 48 mm cable lug width at flange connection  Bolt diameter at flange connection: M10 40 mm x 10 mm | 
| Terminal capacity (copper band) | 
                                                10 mm x 16 mm x 0.8 mm (10x) at box terminal
                                             | 
| Terminal capacity (stranded cable) | 
                                                95 mm² - 300 mm² (1x) at box terminal  120 mm² - 240 mm² at clamp-type terminal 120 mm² - 150 mm² (2x) at double clamp-type terminal 25 mm² - 240 mm² at box terminal | 
| Frequency rating (electronic fuse monitoring) | 
                                                50 - 60 Hz
                                             | 
| Rated operational current | 
                                                400 A (DC-22B)  400 A (AC-21B) 400 A (AC-22B) 400 A (AC-23B) | 
| Operating altitude without derating - max | 
                                                2000 mm
                                             | 
| Permitted power loss per fuse link - max | 
                                                34 W
                                             | 
| Power rating at AC-23, 400 V | 
                                                0 kW
                                             | 
| Rated insulation voltage (Ui) | 
                                                800 VAC
                                             | 
| Rated operating voltage (Ue) at AC - max | 
                                                500 V
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                400 A
                                             | 
| Rated conditional short-circuit rating | 
                                                100 kA (690 V)  120 kA (500 V) | 
| Terminal capacity (copper strip) | 
                                                16 mm x 0.8 mm (6x) - 32 mm x 1 mm (10x) at box terminal
                                             |