Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 160A, box terminals, +residual current circuit-breaker, 30mA, AC/DC sensitive
Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
Catalog Number |
116304
|
Model Code |
NZMH2-A160-FIA30-BT
|
EAN |
4015081160440
|
Product Length/Depth |
293 mm
|
Product Height |
145 mm
|
Product Width |
140 mm
|
Product Weight |
5.58 kg
|
Compliances |
RoHS conform
|
Certifications |
EN 62423: Type B
IEC IEC/EN 60947 VDE 0660 |
Amperage Rating |
160 A
|
Voltage rating |
400 V - 400 V
|
Circuit breaker frame type |
NZM2
|
Features |
Motor drive optional
Protection unit |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
Fixed
Built-in device fixed built-in technique DIN rail (top hat rail) mounting optional |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Equipment heat dissipation, current-dependent |
38.4 W
|
Utilization category |
A (IEC/EN 60947-2)
|
Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
Direction of incoming supply |
Bottom
|
Electrical connection type of main circuit |
Frame clamp
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal) |
Number of poles |
Three-pole
|
Terminal capacity (copper strip) |
Max. 8 segments of 24 mm x 1 mm (2x) at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched) Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched) Max. 10 segments of 16 mm x 0.8 mm at box terminal Min. 2 segments of 9 mm x 0.8 mm at box terminal |
Lifespan, electrical |
6500 operations at 400 V AC-3
5000 operations at 690 V AC-3 6500 operations at 415 V AC-3 7500 operations at 690 V AC-1 10000 operations at 400 V AC-1 10000 operations at 415 V AC-1 |
Functions |
System and cable protection, fire protection, personnel protection
|
Type |
Circuit breaker
|
Special features |
|
Application |
Use in unearthed supply systems at 690 V
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Position of connection for main current circuit |
Front side
|
Rated operational current for specified heat dissipation (In) |
160 A
|
Power loss |
38.4 W
|
Release system |
Thermomagnetic release, AC/DC sensitive earth-fault release
|
Short-circuit total breaktime |
< 10 ms
|
Rated short-time withstand current (t = 0.3 s) |
1.9 kA
|
Rated short-time withstand current (t = 1 s) |
1.9 kA
|
Short-circuit release non-delayed setting - max |
1600 A
|
Short-circuit release non-delayed setting - min |
960 A
|
Terminal capacity (control cable) |
0.75 mm² - 1.5 mm² (2x)
0.75 mm² - 2.5 mm² (1x) |
Terminal capacity (copper busbar) |
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 24 mm x 8 mm direct at switch rear-side connection M8 at rear-side screw connection |
Terminal capacity (copper solid conductor/cable) |
16 mm² (1x) at tunnel terminal
6 mm² - 16 mm² (2x) at box terminal 10 mm² - 16 mm² (1x) direct at switch rear-side connection 10 mm² - 16 mm² (1x) at box terminal 6 mm² - 16 mm² (2x) direct at switch rear-side connection |
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper stranded conductor/cable) |
25 mm² - 185 mm² (1x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal 25 mm² - 70 mm² (2x) at box terminal 25 mm² - 185 mm² (1x) at box terminal 25 mm² - 70 mm² (2x) direct at switch rear-side connection |
Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 185 mm² (1x) at tunnel terminal
|
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
1600 A
|
Instantaneous current setting (Ii) - min |
960 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
160 A
|
Overload current setting (Ir) - min |
125 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
130 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
37.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
5 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
330 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
286 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
105 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
40 kA
|
Standard terminals |
Box terminal
|
Optional terminals |
Connection on rear. Screw terminal. Tunnel terminal
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
330 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Rated insulation voltage (Ui) |
1000 V AC
|