Download document () of 20

021944
Model code: CI44-200

Eaton xEnergy Safety Ci LV systems LV switchgear. Insulated enclosure, top+bottom open, HxWxD=375x375x225mm

General specifications

Product Name
Eaton xEnergy Safety Ci empty enclosure insulated
Catalog Number
021944
EAN
4015080219446
Model Code
CI44-200
Product Length/Depth
225 mm
Product Height
375 mm
Product Width
375 mm
Product Weight
3.128 kg
Compliances
RoHS conform
Certifications
EN 61439-2
EN 62208

Delivery program

Type
Basic enclosure Panel enclosures xEnergy Safety Ci
Color
Gray
Nominal current
1600 A

Technical data - electrical

Circuit integrity
Other

Technical data - mechanical

Unit type
Single unit
Surface finishing
Resistant to corrosion
Surface protection
Other
Surface treatment
Resistant to corrosion
Enclosure material
Plastic
Width in number of modular spacings
15
Mounting depth with mounting plate
200 mm
Mounting method
Surface mounted (plaster)
Material
Non-reinforced polycarbonate (cover)
Glass-fibre reinforced polycarbonate (base)
Halogen free
Degree of protection
Other
IK10
IP65
Number of conduit inlets
100
Number of modules
1
Number of openings (flange plates)
4
Number of rows
0
Built-in depth
200 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Optional
Transparent
None
Chemical resistance
Partly resistant to: Acids > 10 %
Resistant against: acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions
Not resistant to: alkalis, benzene
Saline spray resistance
IEC 60068-2-11
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
27 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
31 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
29 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
53 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
62 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
57 W

Design verification as per IEC/EN 61439 - technical data

Temperature resistance
Temperature resistant: 80 °C (gasket)
Temperature resistant: -40 °C - 120 °C (enclosure)
Temperature resistant: 85 °C (enclosure bolt)
Ambient operating temperature details
-40 °C - 80 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
20 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
UV resistance beneath protective shield
Cover with overpressure release
Flammability characteristics (UL)
V1 (base) (UL94)
V2 (cover) (UL94)
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
Housing prepared for distribution board Two sides closed, can be folded out two sides open Sealable cover fasteners Integrated pressure-relief mechanism for short-circuits
Suitable for
Lightning protection
Outdoor use

Export product specification