Eaton Moeller® series E01 Contact element, 1 N/C, front mount, screw connection
Product Name |
Eaton Moeller® series E01 Accessory Contact element
|
Catalog Number |
090401
|
EAN |
4015080904014
|
Model Code |
E01
|
Product Length/Depth |
6 mm
|
Product Height |
29 mm
|
Product Width |
18 mm
|
Product Weight |
0.003 kg
|
Certifications |
UL Category Control No.: NKCR
UL 508 IEC/EN 60947-5 CSA File No.: 46552 CSA CSA Class No.: 3211-03 CE UL CSA-C22.2 No. 14-05 UL File No.: E29184 IEC/EN 60947 |
Electric connection type |
Screw connection
|
Degree of protection |
IP20, with Insulated ferrule ISH2,8
|
Lifespan, mechanical |
100,000,000 Operations
|
Model |
Top mounting
|
Mounting method |
Front fastening
|
Operating frequency |
3600 Operations/h
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Accessories
|
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Terminal capacity |
0.5 - 1.0 mm²
|
Terminal size |
2.8 x 0.8 mm to DIN 46247 and IEC 60760, Fast-on connectors
2.8 x 0.8 mm to DIN 46244, Blade terminal |
Mounting position |
As required
|
Shock resistance |
40 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms
Mechanical, According to IEC/EN 60068-2-27 |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Rated insulation voltage (Ui) |
250 V
|
Rated operational current (Ie) |
4 A at AC-15, 48 V
4 A at AC-15, 110 V |
Rated operational current (Ie) at AC-15, 24 V |
4 A
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
6 A
|
Rated operational current (Ie) at DC-13, 24 V |
1.5 A
|
Rated operational current (Ie) at DC-13, 42 V |
1 A
|
Rated operational current (Ie) at DC-13, 60 V |
0.8 A
|
Rated operational current (Ie) at DC-13, 110 V |
0.5 A
|
Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.2 A
|
Rated operational voltage (Ue) at AC - max |
250 V
|
Short-circuit protection |
FAZ-B6/1, Fuseless
|
Short-circuit protection rating |
Max. 10 A gG/gL, Fuse, Contacts
|
Actuating force - max |
3 N
|
Connection to SmartWire-DT |
No
|
Connection type |
Blade terminal
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0.1 W
|
Rated operational current for specified heat dissipation (In) |
4 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|