098479
Model code: ZG/I45E-200

Eaton xEnergy Safety Ci LV systems LV switchgear. Meter enclosure, HxWxD=500x375x225mm, IP65

General specifications

Product Name
Eaton xEnergy Safety Ci meter enclosure rail
Catalog Number
098479
EAN
4015080984795
Model Code
ZG/I45E-200
Product Length/Depth
225 mm
Product Height
500 mm
Product Width
375 mm
Product Weight
8.2 kg
Compliances
RoHS conform

Delivery program

Type
Ci insulated enclosure Meter enclosures Prepared enclosures
Accessory/spare part type
Meter rail
Meter enclosures
Color
Gray
Nominal current
1600 A

Technical data - electrical

Circuit integrity
Other

Technical data - mechanical

Unit type
Complete housing
Surface protection
Other
Enclosure material
Plastic
Width in number of modular spacings
17
Mounting depth
186 mm
Mounting method
Surface mounted (plaster)
Degree of protection
IP65
Other
IK10
Number of conduit inlets
104
Number of modules
1
Number of openings (flange plates)
6
Number of rows
0
Built-in depth
200 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Transparent
Optional
None
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890)
35 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
31 W
Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890)
40 W
Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890)
38 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
36 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
33 W
Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890)
71 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
62 W
Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890)
81 W
Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890)
76 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
72 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
67 W

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
30 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
Cover with overpressure release
Fitted with:
Mounting plate
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
Meter rail to DIN 43853 including meter fixing screws and nuts Metric cable entry knockouts in all sides Fixing straps for wall fixing Sealable cover fasteners
Suitable for
Outdoor use
Lightning protection