Eaton Moeller series NZM - Molded Case Circuit Breaker. Molded Case Switch, 3p, 63A
Product Name |
Eaton Moeller series NZM molded case switch
|
Catalog Number |
102681
|
EAN |
4015081025411
|
Model Code |
NS1-63-NA
|
Product Length/Depth |
88 mm
|
Product Height |
145 mm
|
Product Width |
90 mm
|
Product Weight |
1.046 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
CE marking UL listed UL/CSA UL (Category Control Number WJAZ) CSA (File No. 22086) UL (File No. E148671) IEC 60947-2 UL 489 CSA-C22.2 No. 5-09 CSA (Class No. 4652-06) CSA certified Specially designed for North America |
Amperage Rating |
63 A
|
Voltage rating |
690 V - 690 V
|
Circuit breaker frame type |
N1
|
Features |
Protection unit
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
Fixed
DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique |
Equipment heat dissipation, current-dependent |
6.69 W
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Rated current (Iu) |
125 A
|
Current rating (Iu) (UL 489 csa 22.2 no. 5.1) |
125 A
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Switch positions |
I, +, 0
|
Degree of protection |
IP20
In the area of the HMI devices: IP20 (basic protection type) |
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Frame clamp
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal) |
Number of poles |
Three-pole
|
Terminal capacity (copper strip) |
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 9 segments of 9 mm x 0.8 mm at box terminal |
Lifespan, electrical |
10000 operations at 415 V AC-1
7500 operations at 690 V AC-1 10000 operations at 400 V AC-1 |
Functions |
Disconnectors/main switches
|
Type |
Switch-disconnector
|
Special features |
|
Application |
Branch circuits, feeder circuits
|
Position of connection for main current circuit |
Front side
|
Rated operational current for specified heat dissipation (In) |
63 A
|
Power loss |
6.7 W
|
Short-circuit total breaktime |
< 10 ms
|
Short-circuit release non-delayed setting - max |
1250 A
|
Short-circuit release non-delayed setting - min |
1250 A
|
Terminal capacity (copper busbar) |
Min. 12 mm x 5 mm direct at switch rear-side connection
NA: min. 12 mm x 5 mm direct at switch rear-side connection Max. 16 mm x 5 mm direct at switch rear-side connection M6 at rear-side screw connection NA: max. 16 mm x 5 mm direct at switch rear-side connection NA: M6 at rear-side screw connection |
Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) at box terminal NA: 9 - 6 AWG (2x) direct at switch rear-side connection 16 mm² (1x) at tunnel terminal NA: 12 - 6 AWG (1x) at box terminal NA: 6 AWG (1x) at tunnel terminal NA: 12 - 6 AWG (1x) direct at switch rear-side connection 10 mm² - 16 mm² (1x) direct at switch rear-side connection 6 mm² - 16 mm² (2x) direct at switch rear-side connection |
Terminal capacity (aluminum solid conductor/cable) |
10 mm² - 16 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal 10 mm² - 16 mm² (2x) direct at switch rear-side connection |
Terminal capacity (copper stranded conductor/cable) |
NA: 4 - 2/0 AWG/kcmil (1x) at box terminal
10 mm² - 70 mm² (1x) at box terminal NA: 4 - 3/0 AWG/kcmil (1x) at 1-hole tunnel terminal 6 mm² - 25 mm² (2x) at box terminal 25 mm² - 95 mm² (1x) at 1-hole tunnel terminal 25 mm² (2x) direct at switch rear-side connection 25 mm² - 70 mm² (1x) direct at switch rear-side connection |
Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 35 mm² (1x) direct at switch rear-side connection
25 mm² - 95 mm² (1x) at 1-hole tunnel terminal 25 mm² - 35 mm² (2x) direct at switch rear-side connection |
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
1250 A
|
Instantaneous current setting (Ii) - min |
1250 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
0 A
|
Overload current setting (Ir) - min |
0 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
85 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
35 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
10 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
7.5 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
105 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
74 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
17 kA
|
Standard terminals |
Box terminal
|
Optional terminals |
Connection on rear. Screw terminal. Tunnel terminal
|
Rated operating voltage Ue (UL) - max |
480 Y / 277 V
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
187 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Rated insulation voltage (Ui) |
690 V AC
|