Eaton Moeller® series DILM Timer module, 24VAC/DC, 5-100s, off-delayed
Product Name |
Eaton Moeller® series DILM timer module
|
Catalog Number |
104946
|
EAN |
4015081048045
|
Model Code |
DILM32-XTED11-100(RA24)
|
Product Length/Depth |
86 mm
|
Product Height |
38 mm
|
Product Width |
45 mm
|
Product Weight |
0.073 kg
|
Certifications |
CSA-C22.2 No. 14-05
CE CSA UL UL File No.: E29184 DIN EN 61812 IEC/EN 60947 UL Category Control No.: NKCR VDE 0660 CSA File No.: 012528 CSA Class No.: 3211-03 IEC/EN 60947-4-1 UL 508 |
Catalog Notes |
Cannot be combined with top mounting auxiliary contacts
|
Fitted with: |
Suppressor circuits
|
Operating mode |
Electronic
|
Delay time |
50 ms, On-delayed
200 ms, Off-delayed |
Lifespan, mechanical |
3,000,000 Operations (DC operated)
3,000,000 Operations (AC operated) |
Operating frequency |
360 mechanical Operations/h
3600 Operations/h |
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Accessories
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front
|
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Recovery time |
70 ms (after 100 % time delay)
|
Mounting position |
As required (except suspended)
|
Shock resistance |
6 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Ambient operating temperature - min |
-25 °F
|
Ambient operating temperature - max |
60 °F
|
Ambient operating temperature (enclosed) - min |
25 °F
|
Ambient operating temperature (enclosed) - max |
40 °F
|
Ambient storage temperature - min |
40 °F
|
Ambient storage temperature - max |
80 °F
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 1.5) mm²
2 x (0.75 - 1.5) mm² |
Terminal capacity (solid) |
1 x (0.75 - 2.5) mm²
2 x (0.75 - 1.5) mm² |
Terminal capacity (solid/stranded AWG) |
18 - 14
|
Screw size |
M3.5, Terminal screw, Control circuit cables
|
Screwdriver size |
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
2, Terminal screw, Pozidriv screwdriver |
Rated operational current (Ie) |
0.1 A at 220 V, DC-13 L/R - 300 ms (with 1 contact in series)
0.2 A at 60 V, DC-13 L/R - 50 ms (with 1 contact in series) 1 A at 24 V, DC-13 L/R - 300 ms (with 1 contact in series) 0.2 A at 60 V, DC-13 L/R - 300 ms (with 1 contact in series) 3 A at AC-15, 220 V 230 V 240 V 0.2 A at 110 V, DC-13 L/R - 300 ms (with 1 contact in series) 0.2 A at 110 V, DC-13 L/R - 50 ms (with 1 contact in series) 0.1 A at 220 V, DC-13 L/R - 50 ms (with 1 contact in series) 1 A at 24 V, DC-13 L/R - 50 ms (with 1 contact in series) |
Short-circuit current rating (basic rating) |
5 kA, SCCR (UL/CSA)
125 A, max. CB, SCCR (UL/CSA) 125 A, max. Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) |
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA) 10/65 kA, CB, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) |
10/22 kA, CB, SCCR (UL/CSA)
125/125 A, Class J, max. Fuse, SCCR (UL/CSA) 10/100 kA, Fuse, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) |
Short-circuit protection rating |
Max. 4 A gG/gL, fuse, Without welding, Auxiliary and control circuits
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
4 A
|
Switching capacity (auxiliary contacts, general use) |
5 A, 240 V AC, (UL/CSA)
5 A, 24 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
R300, DC operated (UL/CSA)
B300, AC operated (UL/CSA) |
Duty factor |
100 %
|
Pick-up voltage |
0.85 - 1.1 V AC x Uc
0.7 - 1.2 V DC x Uc |
Power consumption (sealing) at DC |
1.8 W
|
Power consumption, sealing, 50 Hz |
2 VA, Coil in a cold state and 1.0 x Us
|
Power consumption, sealing, 60 Hz |
2 VA, Coil in a cold state and 1.0 x Us
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
24 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
24 V
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally open contacts) |
1
|
Safe isolation |
250 V AC, Between auxiliary contacts, According to EN 61140
250 V AC, Between coil and auxiliary contacts, According to EN 61140 |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|