Photo is representative
                                
                                
                                    
                                    Download
                                
                                
                                 
		
	
    
        
        
        
        
        
    
    
    Eaton SPX Variable frequency drive, 600 V AC, 3-phase, 250 kW, IP00, OLED display, FR10
| Product Name | 
                                                Eaton SPX variable frequency drive
                                             | 
| Catalog Number | 
                                                129602
                                             | 
| EAN | 
                                                4015081269297
                                             | 
| Model Code | 
                                                SPX250A0-5A2N1
                                             | 
| Product Length/Depth | 
                                                506 mm
                                             | 
| Product Height | 
                                                1165 mm
                                             | 
| Product Width | 
                                                500 mm
                                             | 
| Product Weight | 
                                                275 kg
                                             | 
| Certifications | 
                                                IEC/EN 61800-3  UL File No.: E134360 RCM CUL CSA-C22.2 No. 14 UL 508C CSA Class No.: 3211-06 DNV IEC/EN61800-5 Safety: EN 61800-5-1: 2003 Certified by UL for use in Canada RoHS, ISO 9001 Specification for general requirements: IEC/EN 61800-2 UL report applies to both US and Canada UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8 CE IEC/EN61800-3 UL | 
| Product Category | 
                                                Variable frequency drives
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| Fitted with: | 
                                                IGBT inverter  Internal DC link Control unit OLED display PC connection | 
| Climatic proofing | 
                                                < 95 % relative humidity, no condensation, no corrosion, no dripping water
                                             | 
| Connection to SmartWire-DT | 
                                                No
                                             | 
| Operating mode | 
                                                Optional: Vector control with feedback (CLV)  Sensorless vector control (SLV) U/f control | 
| Frame size | 
                                                FR10
                                             | 
| Altitude | 
                                                Above 1000 m with 1 % performance reduction per 100 m  Max. 1000 m Max. 3000 m | 
| Application in domestic and commercial area permitted | 
                                                Yes
                                             | 
| Application in industrial area permitted | 
                                                Yes
                                             | 
| Ambient operating temperature - max | 
                                                40 °C
                                             | 
| Ambient operating temperature - min | 
                                                -10 °C
                                             | 
| Ambient operating temperature at 150% overload - max | 
                                                40 °C
                                             | 
| Ambient operating temperature at 150% overload - min | 
                                                -10 °C
                                             | 
| Ambient storage temperature - max | 
                                                70 °C
                                             | 
| Ambient storage temperature - min | 
                                                -40 °C
                                             | 
| Mounting position | 
                                                Vertical
                                             | 
| Relative symmetric net frequency tolerance | 
                                                10 %
                                             | 
| Relative symmetric net voltage tolerance | 
                                                10 %
                                             | 
| Protection | 
                                                Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
                                             | 
| Heat dissipation details | 
                                                Operation (with 150 % overload)
                                             | 
| Rated operational power at 690 V, 50 Hz, 3-phase | 
                                                250 kW
                                             | 
| Rated operational power at 690 V, 50 Hz, 3-phase, 110% overload | 
                                                315 kW
                                             | 
| Resolution | 
                                                0.01 Hz (Frequency resolution, setpoint value)
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                0 W
                                             | 
| Voltage rating - max | 
                                                690 VAC
                                             | 
| Communication interface | 
                                                CANopen®, optional  PROFIBUS-DP DeviceNet, optional LonWorks, optional BACnet/IP, optional Modbus-TCP, optional BACnet MS/TP, optional EtherCAT, optional Ethernet IP, optional Modbus-RTU, optional PROFINET, optional | 
| Converter type | 
                                                U converter
                                             | 
| Degree of protection | 
                                                IP00  NEMA Other | 
| Protocol | 
                                                PROFIBUS  Other bus systems DeviceNet LON CAN TCP/IP Data-Highway | 
| Assigned motor current IM at 690 V, 50 Hz, 110% overload | 
                                                316 A
                                             | 
| Assigned motor current IM at 690 V, 50 Hz, 150% overload | 
                                                253 A
                                             | 
| Assigned motor current IM at 690 V, 60 Hz, 110% overload | 
                                                251 A
                                             | 
| Assigned motor current IM at 690 V, 60 Hz, 150% overload | 
                                                211 A
                                             | 
| System configuration type | 
                                                AC supply systems with earthed center point
                                             | 
| Electromagnetic compatibility | 
                                                1st and 2nd environments (according to EN 61800-3)
                                             | 
| Assigned motor power at 690 V, 60 Hz, 3-phase | 
                                                250 HP
                                             | 
| Assigned motor power at 690 V, 60 Hz, 3-phase, 110 % overload | 
                                                300 HP
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                6250 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Functions | 
                                                4-quadrant operation possible
                                             | 
| Output voltage (U2) | 
                                                690 V AC, 3-phase  600 V AC, 3-phase | 
| Number of inputs (analog) | 
                                                2
                                             | 
| Number of inputs (digital) | 
                                                6
                                             | 
| Radio interference class | 
                                                C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
                                             | 
| Number of outputs (digital) | 
                                                1
                                             | 
| Number of phases (input) | 
                                                3
                                             | 
| Number of relay outputs | 
                                                2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
                                             | 
| Number of phases (output) | 
                                                3
                                             | 
| Rated control supply voltage | 
                                                10 V DC (Us, max. 10 mA)
                                             | 
| Rated control voltage (Uc) | 
                                                24 V DC (external, max. 250 mA)
                                             | 
| Supply frequency | 
                                                50/60 Hz
                                             | 
| Mains voltage - max | 
                                                690 V
                                             | 
| Mains voltage - min | 
                                                525 V
                                             | 
| Nominal output current I2N | 
                                                325 A
                                             | 
| Number of HW-interfaces (industrial ethernet) | 
                                                0
                                             | 
| Number of HW-interfaces (other) | 
                                                1
                                             | 
| Number of HW-interfaces (parallel) | 
                                                0
                                             | 
| Number of HW-interfaces (RS-232) | 
                                                0
                                             | 
| Number of HW-interfaces (RS-422) | 
                                                0
                                             | 
| Number of HW-interfaces (RS-485) | 
                                                1
                                             | 
| Number of HW-interfaces (serial TTY) | 
                                                0
                                             | 
| Number of HW-interfaces (USB) | 
                                                0
                                             | 
| Number of interfaces (PROFINET) | 
                                                0
                                             | 
| Number of outputs (analog) | 
                                                1
                                             | 
| Output at linear load at rated output voltage - max | 
                                                250 kW
                                             | 
| Output at quadratic load at rated output voltage - max | 
                                                315 kW
                                             | 
| Output frequency - max | 
                                                320 Hz
                                             | 
| Output frequency - min | 
                                                0 Hz
                                             | 
| Output voltage - max | 
                                                690 V
                                             | 
| Suitable for | 
                                                Branch circuits, (UL/CSA)
                                             | 
| Switching frequency | 
                                                1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
                                             | 
| Rated operational voltage | 
                                                600 V AC, 3-phase  690 V AC, 3-phase | 
| Rated frequency - max | 
                                                66 Hz
                                             | 
| Rated frequency - min | 
                                                45 Hz
                                             | 
| Rated operational current (Ie) at 110% overload | 
                                                325 A
                                             | 
| Rated operational current (Ie) at 150% overload | 
                                                261 A
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                261 A
                                             |