Photo is representative
Download
Eaton DM1 Variable frequency drive, 600 V AC, 3-phase, 7.5 A, 4 kW, IP20/NEMA0, 7-digital display assembly, Setpoint potentiometer, Brake chopper, FS2
Product Name |
Eaton DM1 Variable frequency drive
|
Catalog Number |
3-5051-005A
|
EAN |
4015081981090
|
Model Code |
DM1-357D5NB-S20S-EM
|
Product Length/Depth |
180 mm
|
Product Height |
220 mm
|
Product Width |
109 mm
|
Product Weight |
2.6 kg
|
Certifications |
RoHS, ISO 9001
UL UL Category Control No.: NMMS, NMMS7 Certified by UL for use in Canada IEC/EN 61800-2 IEC/EN61800-3 UkrSEPRO IEC/EN 61800-3 C-Tick UL Listed UL 508C IEC/EN61800-5 CE marking CSA-C22.2 No. 274-13 UL File No.: E134360 IEC/EN 61800-5-1 CUL CE UL report applies to both US and Canada EAC CSA-C22.2 No. 274-17 |
Air volume capacity |
64 m³/h
|
Communication interface |
Modbus TCP, built in
Modbus RTU, built in DeviceNet, optional SmartWire-DT, optional BACnet MS/TP, built in Ethernet IP, built in BACnet TCP PROFIBUS, optional CANopen®, optional |
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Features |
Parameterization: Fieldbus
Temperature-controlled fan Parameterization: Keypad Parameterization: Power Xpert inControl |
Fitted with: |
IGBT inverter
7-digital display assembly Internal DC link Brake chopper Setpoint potentiometer Breaking resistance Control unit PC connection |
Frame size |
FS2
|
Mounting position |
Vertical
|
Number of slots |
1 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: with external filter, for conducted emissions only |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 3000 m Max. 2000 m for Corner Grounded TN Systems |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Heat dissipation at current/speed |
110 W at 100% current and 0% speed
140 W at 50% current and 0% speed 160 W at 100% current and 90% speed 60 W at 25% current and 0% speed 70 W at 100% current and 50% speed 70 W at 25% current and 50% speed 80 W at 50% current and 50% speed 90 W at 50% current and 90% speed |
Input current ILN at 110% overload |
9.3 A
|
Input current ILN at 150% overload |
7 A
|
Mains current distortion |
40 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
525 V
|
Mains voltage - max |
600 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Torque regulation PM motors Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
600 V AC, 3-phase
|
Overload current IL at 110% overload |
11 A
|
Overload current IL at 150% overload |
11.25 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
10 A
|
Rated operational current (Ie) at 150% overload |
7.5 A
|
Rated operational power at 600 V, 50 Hz, 3-phase |
4 kW
|
Rated operational power at 600 V, 50 Hz, 3-phase, 110% overload |
5.5 kW
|
Rated operational voltage |
600 V AC, 3-phase
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
600 V
|
Assigned motor current IM at 550 - 600 V, 60 Hz, 150% overload |
6.1 A
|
Assigned motor current IM at 600 V, 60 Hz, 110% overload |
9 A
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
5 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase, 110 % overload |
7.5 HP
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit Adjustable to 150 %, DC - Main circuit |
Number of inputs (analog) |
1
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
Equipment heat dissipation, current-dependent Pvid |
170 W
|
Rated operational current for specified heat dissipation (In) |
10 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|