Eaton Moeller® series EMR6 Phase monitoring relays, On- and Off-delayed, 380 V AC, 50/60 Hz

ข้อมูลทั่วไป

Product Name
Eaton Moeller® series EMR6 Phase monitoring relay
Catalog Number
184777
EAN
4015081788132
Product Length/Depth
103.7 mm
Product Height
85.6 mm
Product Width
22.5 mm
Product Weight
0.16 kg
Certifications
GL
CSA
IEC
CCC
UL

คุณสมบัติและการทำงาน

Electric connection type
Screw connection
Features
Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages
Functions
On- and Off-delayed
Under voltage detection
Over voltage detection
Phase failure detection
Monitoring function
Phase failure
Overvoltage
Undervoltage
Phase sequence (can be deactivated)
Phase sequence monitoring
Voltage measurement - min
380 V
Voltage measurement - max
380 V

ข้อมูลทั่วไป

Degree of protection
Terminals: IP20
Enclosure: IP50
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMR Measuring and monitoring relays
Product category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of Undervoltage: F2 red, solid light
Status indication of Supply voltage: Yellow, solid light
Status indication of Overvoltage: Red LED (F1 on)
Status indication of Phase failure: F1 red, solid light and F2 red, flashing light
Status indication of Undervoltage: Red LED (F2 on)
Status indication of Overvoltage: F1 red, solid light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of Relay energized: Yellow, solid light (R/T)
Status indication of Supply voltage: Yellow LED
Status indication of Delay time running: Yellow, flashing light (R/T)
Suitable for
Three-phase networks
Type
Phase monitoring relay
Voltage type
AC

สภาวะทางสภาพภูมิอากาศ

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30

ความเข้ากันได้ของแม่เหล็กไฟฟ้า

Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4

ความจุเทอร์มินอล

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
0.8 Nm, Screw terminals
Min. 0.6 Nm, Screw terminals

วงรอบเวลา

Delay time
Start-up delay fixed Ts = 250 ms
Adjustable tripping delay Tv = 0 - 30 s
Timing cycle
0.06 %/°C, Time error within temperature range
0.5 %, Time error within supply voltage
0.5 % Error within supply voltage (Measuring circuits)

แหล่งจ่ายไฟฟ้า

Duty factor
100 %, Power supply
Power consumption
18 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
380 V
Rated control supply voltage (Us) at AC, 50 Hz - max
380 V
Rated control supply voltage (Us) at AC, 60 Hz - min
380 V
Rated control supply voltage (Us) at AC, 60 Hz - max
380 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
380 V, 50/60 Hz
Voltage tolerance
0.85 x Uc
1.1 x Uc

วงจรการวัด

Hysteresis
0 - 5 %
Measuring cycle
100 ms
Temperature error
0.06 %/°C, Measuring circuits

หน้าสัมผัสเอาต์พุตรีเลย์

Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
100,000 Operation (at 230 V, AC-12, 4 A)
Rated operational current (Ie)
2 A at DC-13, 24 V
3 A at AC-15, 230 V
4 A at DC-12, 24 V
4 A at AC-12, 230 V
Rated operational voltage (Ue) at AC - max
250 V

ส่งออกข้อมูลจำเพาะของผลิตภัณฑ์

Installation instructions

บันทึกการใช้งาน

โบรชัวร์