Eaton DG1 Variable frequency drive, 230 V AC, 3-phase, 75 A, 22 kW, IP54/NEMA12, DC link choke
| Product Name |
Eaton DG1 variable frequency drive
|
| Catalog Number |
9701-4107-00P
|
| EAN |
4015081734931
|
| Product Length/Depth |
294 mm
|
| Product Height |
630 mm
|
| Product Width |
237.7 mm
|
| Product Weight |
34 kg
|
| Certifications |
CSA-C22.2 No. 274-13
EAC CE CUL UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 Specification for general requirements: IEC/EN 61800-2 UkrSEPRO Certified by UL for use in Canada IEC/EN61800-3 IEC/EN61800-5 C-Tick UL UL report applies to both US and Canada RoHS, ISO 9001 Safety requirements: IEC/EN 61800-5 UL508 IEC/EN 61800-3 |
| Model Code |
DG1-32075FN-C54C
|
| Features |
Externally accessible fan
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
| Air volume capacity |
260 m³/h
|
| Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
C3 ≤ 50 m, Radio interference level, maximum motor cable length 200 m, screened, maximum permissible, Motor feeder |
| Degree of protection |
IP54
NEMA 12 |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Environmental class |
3C2, 3S2 (Air quality)
|
| Fitted with: |
IGBT inverter
DC link choke Radio interference suppression filter Multi-line graphic display PC connection Control unit Internal DC link Additional PCB protection |
| Frame size |
FS4
|
| Mounting position |
Vertical
|
| Number of slots |
2 (expansion)
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
| Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
| Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) UPS drop test (for weights inside the UPS frame) |
| Suitable for |
Branch circuits, (UL/CSA)
|
| Vibration |
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
| Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 2000 m for Corner Grounded TN Systems Max. 1000 m Max. 3000 m |
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature - max |
50 °C
|
| Ambient operating temperature at 150% overload - min |
-30 °C
|
| Ambient operating temperature at 150% overload - max |
50 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
| Efficiency |
98 % (η)
|
| Heat dissipation at current/speed |
261 W at 25% current and 0% speed
295 W at 25% current and 50% speed 312 W at 100% current and 50% speed 401 W at 50% current and 50% speed 447 W at 50% current and 90% speed 596 W at 100% current and 0% speed 716 W at 50% current and 0% speed 842 W at 100% current and 90% speed |
| Input current ILN at 110% overload |
78 A
|
| Input current ILN at 150% overload |
69.4 A
|
| Leakage current at ground IPE - max |
6.2 mA
|
| Mains current distortion |
25.6 %
|
| Mains switch-on frequency |
Maximum of one time every 60 seconds
|
| Mains voltage - min |
208 V
|
| Mains voltage - max |
240 V
|
| Operating mode |
Sensorless vector control (SLV)
Speed control with slip compensation U/f control Torque regulation |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
400 Hz
|
| Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
| Overload current IL at 110% overload |
96.8 A
|
| Overload current IL at 150% overload |
112.5 A
|
| Rated conditional short-circuit current (Iq) |
100 kA
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
45 Hz
|
| Rated frequency - max |
66 Hz
|
| Rated operational current (Ie) at 110% overload |
88 A
|
| Rated operational current (Ie) at 150% overload |
75 A
|
| Rated operational power at 220/230 V, 50 Hz, 1-phase |
22 kW
|
| Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
22 kW
|
| Rated operational voltage |
230 V AC, 3-phase
240 V AC, 3-phase |
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
110 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
3.6 kHz, 1 - 10 kHz adjustable, fPWM, Power section, Main circuit
|
| System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
| Voltage rating - max |
240 VAC
|
| Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
68 A
|
| Assigned motor current IM at 230 V, 50 Hz, 110% overload |
71 A
|
| Assigned motor current IM at 230 V, 50 Hz, 150% overload |
71 A
|
| Assigned motor current IM at 230 V, 60 Hz, 110% overload |
80 A
|
| Assigned motor power at 230/240 V, 60 Hz, 1-phase |
25 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
30 HP
|
| Apparent power at 230 V |
35.1 kVA
|
| Apparent power at 240 V |
36.6 kVA
|
| Braking resistance |
3.3 Ω
|
| Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 % (I/Ie), DC - Main circuit Max. 30 % MN, Standard - Main circuit Adjustable to 150 %, DC - Main circuit |
| Switch-on threshold for the braking transistor |
425 VDC
|
| Number of inputs (analog) |
2
|
| Number of inputs (digital) |
8
|
| Number of outputs (analog) |
2
|
| Number of outputs (digital) |
1
|
| Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
| Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
| Communication interface |
Modbus TCP, built in
DeviceNet, optional PROFIBUS, optional BACnet MS/TP, built in Ethernet IP, built in Modbus RTU, built in SmartWire-DT, optional CANopen®, optional |
| Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
| Protocol |
PROFIBUS
DeviceNet BACnet Other bus systems PROFINET IO CAN TCP/IP EtherNet/IP MODBUS |
| Equipment heat dissipation, current-dependent Pvid |
830 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
75 A
|
| Static heat dissipation, non-current-dependent Pvs |
17.1 W
|
| Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|