Eaton DC1 Variable frequency drive, 115 V AC, single-phase, 2.3 A, 0.37 kW, IP66/NEMA 4X, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199394
|
Product Length/Depth |
162 mm
|
Product Height |
232 mm
|
Product Width |
161 mm
|
Product Weight |
2.5 kg
|
Certifications |
CE marking
EAC RCM CSA-C22.2 No. 14 UL 508C UL Category Control No.: NMMS, NMMS7 UL Listed UL File No.: E172143 IEC/EN61800-5 CUL Certified by UL for use in Canada RoHS, ISO 9001 IEC/EN 61800-5-1 UL CE UL report applies to both US and Canada IEC/EN 61800-2 UkrSEPRO IEC/EN 61800-3 |
Features |
Parameterization: drivesConnect mobile (App)
Parameterization: drivesConnect Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
Internal DC link
PC connection Additional PCB protection UV resistance 7-digital display assembly Control unit Local controls IGBT inverter |
Cable length |
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder 75 m, unscreened, maximum permissible, Motor feeder 50 m, screened, maximum permissible, Motor feeder |
Communication interface |
OP-Bus (RS485), built in
SmartWire-DT, optional Modbus RTU, built in CANopen®, built in |
Connection to SmartWire-DT |
No
|
Degree of protection |
IP66
NEMA 4X |
Frame size |
FS1
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
EtherNet/IP
MODBUS CAN Other bus systems |
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Input current ILN at 150% overload |
7.8 A
|
Leakage current at ground IPE - max |
4.8 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
110 V
|
Mains voltage - max |
115 V
|
Operating mode |
Speed control with slip compensation
Synchronous reluctance motors U/f control BLDC motors PM motors Sensorless vector control (SLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
230 V AC, 3-phase
|
Overload current IL at 150% overload |
3.45 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
2.3 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
0.37 kW
|
Rated operational voltage |
115 V AC, 1-phase
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 % IH
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
120 V
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
2 A
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|