知識搜尋
下載文件 () / 20
我們讓至關重要的事情運作*

190872
FAZ-C8/4-RT

Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. Miniature circuit breaker (MCB), 8 A, 4p, characteristic: C, ring tongue

常用規格

Product Name
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
Catalog Number
190872
Product Length/Depth
105 mm
Product Height
75.5 mm
Product Width
70.8 mm
Product Weight
0.489 kg
Compliances
RoHS conform
Certifications
IEC 60947-2
CE marking
UL (Category Control Number DIVQ)
CSA (Class No. 1432-01)
IEC/EN 60947-2
UL (File No. E235139)
UL 489
Specially designed for North America, suitable as BCPD
UL 489, CSA C22.2 No. 5
CSA (File No. 204453)
CSA-C22.2 No. 5-09
North America (UL listed, CSA certified)
EN45545-2
IEC 61373

交付計畫

Application
  • Industrial and commercial applications
  • Utilities and OEM control panels
  • Renewable energy installations
  • IT and data centre auxiliary circuits
  • Railway and transportation systems
  • Branch circuits and power distribution panels
  • HVAC/R and motor branch circuits
  • A2L refrigerant environments, etc.
Number of poles
Four-pole
Number of poles (total)
4
Number of poles (protected)
4
Tripping characteristic
C
Release characteristic
C
Amperage Rating
8 A
Nominal current
8 A
Type
  • FAZ-RT
  • Miniature circuit breaker

技術資料 - 電氣

Voltage type
AC
Voltage rating
480Y/277 V AC
Voltage rating (IEC/EN 60947-2)
  • !
  • 240/415 V AC
Voltage rating (UL)
  • !
  • 480Y/277 V AC
Voltage rating (UL CSA 13)
480 Y/277 V AC
Rated operational voltage (Ue) - max
440 VAC
Operational voltage (IEC/EN 60947-2) - max
440 VAC
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2) at max voltage rating
15 kA
Rated switching capacity (IEC/EN 60947-2)
25 kA
Breaking capacity
10 kA (UL489)
Rated service short-circuit breaking capacity (IEC/EN 60947-2) - Ics
7.5 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V
25 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V
25 kA
Selectivity class
3
Overvoltage category
III
Pollution degree
2
Lifespan, electrical
min. 1500 operations
min. 6000 operations (UL)
Direction of incoming supply
Bidirectional

技術資料 - 機械

Frame
45 mm
Width in number of modular spacings
4
Built-in depth
65.5 mm
Mounting width per pole
17.7 mm
Mounting width
17.7 mm
Mounting Method
Top-hat rail IEC/EN 60715
Mounting position
As required
Degree of protection
IP20
IP40 (when fitted)
UL/CSA Type: -
IP20 (IEC)
Terminals (top and bottom)
  • Screw-type with pressure plate
  • Ring tongue compatible
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Terminal protection
Touch-safe (EN 50274)
Contact position indicator color
Red / green
Tightening torque
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
UL: 4 Nm (36 lb-in) for AWG 6
Max. 2.4 Nm
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
Lifespan, mechanical
10000 operations

設計驗證符合 IEC/EN - 技術資料

Rated operational current for specified heat dissipation (In)
8 A
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C

設計驗證符合 IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

額外資訊

Current limiting class
3
Features
Additional equipment possible
Functional group
Overcurrent protection
Functions
Overload protection
Short Circuit protection
Internal resistance at room temperature (single-pole, 50 Hz)
19 mΩ
Special features
  • !
  • !

匯出產品規格

Serial Number Verified :
Authenticated: ✓
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

驗證產品

請輸入您的 16-17 位數的序號
您輸入的序號不應包含特殊字元。 您輸入的序號不正確,它應該是 16 位或 17 位的序號。 找不到您輸入的序號。請重試或 回報此問題 以獲得進一步協助。 您輸入的序號與產品不符。請檢查您的產品序號並重試。 點擊 此處 前往您所輸入序號的產品頁面 伊頓已知該序號為「可疑」,請重試或 回報此問題 以獲得進一步協助。
序號
重設 伊頓已知該序號為「可疑」,請重試或 回報此問題 以獲得進一步協助。 伊頓無法辨識此序號,此序號無效。請使用本表單以 回報此問題 以獲得進一步協助。
請輸入 6 位數驗證碼
您輸入的產品有問題!請重試或 回報此問題 以獲得進一步協助。 您輸入的驗證碼與我們的序號記錄不符。請重試,或 回報此問題 以獲得進一步協助。 無效的驗證碼。長度必須為 6 個字元 回報此問題 以獲得進一步協助。 驗證碼為必填 回報此問題 以獲得進一步協助。
驗證之前請先完成 Captcha 驗證。
x
回報問題
請輸入您的全名。
x
感謝您,您的問題已提交,我們的產品團隊將盡快聯絡您。