Eaton Moeller series xPole (Style 5) - mMCT MCB. Circuit-breaker, 25 A, 3p, Type C characteristic
| Product Name |
Eaton Moeller series xPole (Style 5) - mMCT MCB
|
| Catalog Number |
158317
|
| Model Code |
mMCT-C25/3
|
| EAN |
4015081548965
|
| Product Length/Depth |
90 mm
|
| Product Height |
75 mm
|
| Product Width |
81 mm
|
| Product Weight |
0.706 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC/EN 60947-2
|
| Global Catalog |
158317
|
| Product Type |
MCB
|
| Used with |
Miniature circuit breaker
mMCT |
| Amperage Rating |
25 A
|
| Voltage rating |
230 V AC / 400 V AC
|
| Features |
Additional equipment possible
|
| Frame |
45 mm
|
| Pollution degree |
2
3 |
| Lifespan, mechanical |
20000 operations
|
| Mounting Method |
Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715
|
| Degree of protection |
IP20
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Functional group |
Overcurrent protection
|
| Terminals (top and bottom) |
Screw-type with pressure plate
|
| Tripping characteristic |
C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Built-in depth |
65.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
50 mm²
|
| Connectable conductor cross section (multi-wired) - min |
2.5 mm²
|
| Connectable conductor cross section (solid-core) - max |
50 mm²
|
| Connectable conductor cross section (solid-core) - min |
2.5 mm²
|
| Current limiting class |
3
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Internal resistance at room temperature (single-pole, 50 Hz) |
4.1 mΩ
|
| Nominal current |
25 A
|
| Direction of incoming supply |
Bidirectional
|
| Width in number of modular spacings |
4.5
|
| Voltage rating (IEC/EN 60947-2) |
230/400 V AC
|
| Voltage rating at DC |
60 V DC (per pole)
|
| Voltage type |
AC
|
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Number of poles |
Three-pole
|
| Lifespan, electrical |
10000 operations
|
| Release characteristic |
C
|
| Type |
|
| Special features |
|
| Application |
|
| Mounting width per pole |
27 mm
|
| Number of poles (protected) |
3
|
| Number of poles (total) |
3
|
| Operational voltage (IEC/EN 60947-2) - max |
400 VAC
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational current for specified heat dissipation (In) |
25 A
|
| Rated operational voltage (Ue) - max |
400 V
|
| Rated service short-circuit breaking capacity (IEC/EN 60947-2) - Ics |
20 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
25 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
25 kA
|
| Rated switching capacity (IEC/EN 60947-2) |
25 kA
|
| Power loss |
7.8 W
|