Eaton xEnergy Safety Ci LV systems LV switchgear. Insulated enclosure, top+bottom open, HxWxD=750x375x275mm
| Product Name | 
                                                Eaton xEnergy Safety Ci empty enclosure insulated
                                             | 
| Catalog Number | 
                                                083642
                                             | 
| EAN | 
                                                4015080836421
                                             | 
| Product Length/Depth | 
                                                275 mm
                                             | 
| Product Height | 
                                                750 mm
                                             | 
| Product Width | 
                                                375 mm
                                             | 
| Product Weight | 
                                                6.13 kg
                                             | 
| Compliances | 
                                                RoHS conform
                                             | 
| Certifications | 
                                                EN 62208  EN 61439-2 | 
| Model Code | 
                                                CI48-250
                                             | 
| Special features | 
                                                Housing prepared for distribution board
Two sides closed, can be folded out
two sides open
Sealable cover fasteners
Integrated pressure-relief mechanism for short-circuits
                                             | 
| Type | 
                                                Basic enclosure
Panel enclosures
xEnergy Safety Ci
                                             | 
| Features | 
                                                UV resistance beneath protective shield  Cover with overpressure release | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.13 Mechanical function | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Lower part: 960 °C / cover: 850 °C
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Not relevant to indoor installations.
                                             | 
| 10.2.5 Lifting | 
                                                40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
                                             | 
| 10.2.6 Mechanical impact | 
                                                IK10
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                IP65
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.5 Protection against electric shock | 
                                                Protection class 2, therefore not applicable.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Ui = 1000 V AC
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                8 kV
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Meets the product standard's requirements.
                                             | 
| Surface finishing | 
                                                Resistant to corrosion
                                             | 
| Degree of protection | 
                                                Other  IP65 IK10 | 
| Enclosure material | 
                                                Plastic
                                             | 
| Surface protection | 
                                                Other
                                             | 
| Chemical resistance | 
                                                Resistant against: acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions  Partly resistant to: Acids > 10 % Not resistant to: alkalis, benzene | 
| Circuit integrity | 
                                                Other
                                             | 
| Unit type | 
                                                Single unit
                                             | 
| Built-in depth | 
                                                250 mm
                                             | 
| Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) | 
                                                52 W
                                             | 
| Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) | 
                                                44 W
                                             | 
| Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) | 
                                                48 W
                                             | 
| Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) | 
                                                105 W
                                             | 
| Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) | 
                                                88 W
                                             | 
| Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) | 
                                                96 W
                                             | 
| Color | 
                                                Gray
                                             | 
| Cover/door color | 
                                                Transparent
                                             | 
| Cover/door model | 
                                                Closed
                                             | 
| Cover/door type | 
                                                Optional  Transparent None | 
| Number of openings (flange plates) | 
                                                6
                                             | 
| Plate thickness (cabinet) | 
                                                6 mm
                                             | 
| Plate thickness (cover/door) | 
                                                6 mm
                                             | 
| RAL-number | 
                                                7035
                                             | 
| Width in number of modular spacings | 
                                                17
                                             | 
| Ambient operating temperature details | 
                                                -40 °C - 80 °C
                                             | 
| Material | 
                                                Halogen free  Glass-fibre reinforced polycarbonate (base) Non-reinforced polycarbonate (cover) | 
| Mounting method | 
                                                Surface mounted (plaster)
                                             | 
| Number of rows | 
                                                0
                                             | 
| Functions | 
                                                Extension possible
                                             | 
| Temperature resistance | 
                                                Temperature resistant: 80 °C (gasket)  Temperature resistant: -40 °C - 120 °C (enclosure) Temperature resistant: 85 °C (enclosure bolt) | 
| Flammability characteristics (UL) | 
                                                V1 (base) (UL94)  V2 (cover) (UL94) | 
| Protection class | 
                                                II
                                             | 
| Number of modules | 
                                                1
                                             | 
| Surface treatment | 
                                                Resistant to corrosion
                                             | 
| Internal depth | 
                                                250 mm
                                             | 
| Mounting depth with mounting plate | 
                                                250 mm
                                             | 
| Nominal current | 
                                                1600 A
                                             | 
| Number of conduit inlets | 
                                                0
                                             | 
| Suitable for | 
                                                Lightning protection  Outdoor use | 
| Saline spray resistance | 
                                                IEC 60068-2-11
                                             | 
| Enclosure material quality | 
                                                Other
                                             | 
| Type of coating | 
                                                Other
                                             |