Download document () of 20

168105
Model code: SOL30X6-SAFETY-MV-U(230V50HZ)

Eaton Moeller® series SOL30 Safety Fireman's switch, for 6 strings, 25A, MV

General specifications

Product Name
Eaton Moeller® series SOL30 Safety Fireman's switch
Catalog Number
168105
EAN
4015081646746
Product Length/Depth
225 mm
Product Height
405 mm
Product Width
500 mm
Product Weight
9.5 kg
Certifications
IEC/EN 60 947-3
Model Code
SOL30X6-SAFETY-MV-U(230V50HZ)

Product specifications

Application
  • Residential buildings
  • Utility buildings
Product Category
  • Fireman's Switch
  • Switchgear for photovoltaic systems
Features
Complete device in housing
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
0 (off) position
Retraction in 0-position
Operating frequency
120 Operations/h
Pollution degree
3
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Enclosure material
Plastic
Rated impulse withstand voltage (Uimp)
8000 V
Utilization category
DC-21 A
DC-PV1 (EN 60947-3)
DC-PV2 (EN 60947-3)
Actuator type
Turn button
Ambient operating temperature - max
60 °C
Ambient operating temperature - min
-25 °C
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
1
Number of auxiliary contacts (normally open contacts)
1
Rated short-time withstand current (Icw)
0.36 kA
Electrical connection type of main circuit
Screw connection
Connection type
M12, Inputs
M12, Outputs
Overvoltage category
III
Number of poles
Two-pole
Degree of protection
IP65
Model
On/Off switch
Degree of protection (front side)
IP65
NEMA Other
Lifespan, mechanical
100,000 Operations
Rated operational current (Ie)
26 A at DC-PV1
10 A at DC-PV2
Lifespan, electrical
1,500 Operations
Resistance
7 mΩ (internal)
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0 A
Suitable for
Ground mounting
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - max
1000 V
Rated uninterrupted current (Iu)
30 A
Rated short-circuit making capacity (Icm)
0.32 kA (up to 440 V, 50/60 Hz)