Eaton Moeller® series DILK Contactor for capacitors, with series resistors, 12.5 kVAr, 190 V 50 Hz, 220 V 60 Hz
| Product Name | 
                                            
                                            
                                             
                                                Eaton Moeller® series DILK capacity contactor
                                             
                                         | 
                                    
| Catalog Number | 
                                            
                                            
                                             
                                                293986
                                             
                                         | 
                                    
| EAN | 
                                            
                                            
                                             
                                                4015082939861
                                             
                                         | 
                                    
| Product Length/Depth | 
                                            
                                            
                                             
                                                138 mm
                                             
                                         | 
                                    
| Product Height | 
                                            
                                            
                                             
                                                135 mm
                                             
                                         | 
                                    
| Product Width | 
                                            
                                            
                                             
                                                45 mm
                                             
                                         | 
                                    
| Product Weight | 
                                            
                                            
                                             
                                                0.51 kg
                                             
                                         | 
                                    
| Certifications | 
                                            
                                            
                                             
                                                IEC/EN 60947-4-1  
                                        UL 60947-4-1 CSA File No.: 012528 UL Category Control No.: NLDX UL File No.: E29096 UL CE CSA Class No.: 3211-04 CSA-C22.2 No. 60947-4-1-14 IEC/EN 60947 CSA  | 
                                    
| Model Code | 
                                            
                                            
                                             
                                                DILK12-11(190V50HZ,220V60HZ)
                                             
                                         | 
                                    
| Fitted with: | 
                                            
                                            
                                             
                                                Series resistors
                                             
                                         | 
                                    
| Application | 
                                            
                                            
                                             
                                                Contactors for power factor correction
                                             
                                         | 
                                    
| Connection | 
                                            
                                            
                                             
                                                Screw terminals
                                             
                                         | 
                                    
| Lifespan, electrical | 
                                            
                                            
                                             
                                                150,000 Operations
                                             
                                         | 
                                    
| Operating frequency | 
                                            
                                            
                                             
                                                120 Operations/h
                                             
                                         | 
                                    
| Product category | 
                                            
                                            
                                             
                                                DILK Contactors for capacitors
                                             
                                         | 
                                    
| Protection | 
                                            
                                            
                                             
                                                Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
                                             
                                         | 
                                    
| Voltage type | 
                                            
                                            
                                             
                                                AC
                                             
                                         | 
                                    
| Ambient operating temperature - min | 
                                            
                                            
                                             
                                                -25 °C
                                             
                                         | 
                                    
| Ambient operating temperature - max | 
                                            
                                            
                                             
                                                60 °C
                                             
                                         | 
                                    
| Ambient operating temperature (enclosed) - min | 
                                            
                                            
                                             
                                                -25 °C
                                             
                                         | 
                                    
| Ambient operating temperature (enclosed) - max | 
                                            
                                            
                                             
                                                40 °C
                                             
                                         | 
                                    
| Emitted interference | 
                                            
                                            
                                             
                                                According to EN 60947-1
                                             
                                         | 
                                    
| Interference immunity | 
                                            
                                            
                                             
                                                According to EN 60947-1
                                             
                                         | 
                                    
| Terminal capacity (flexible with ferrule) | 
                                            
                                            
                                             
                                                1 x (0.75 - 16) mm², Main cables
                                             
                                         | 
                                    
| Terminal capacity (solid) | 
                                            
                                            
                                             
                                                1 x (0.75 - 16) mm², Main cables
                                             
                                         | 
                                    
| Terminal capacity (solid/stranded AWG) | 
                                            
                                            
                                             
                                                18 - 6, Main cables
                                             
                                         | 
                                    
| Terminal capacity (stranded) | 
                                            
                                            
                                             
                                                1 x 16 mm², Main cables
                                             
                                         | 
                                    
| Rated operational power at AC-6B, 220/230 V, 50 Hz | 
                                            
                                            
                                             
                                                7.5 kVA
                                             
                                         | 
                                    
| Rated operational power at AC-6B, 380/400 V, 50 Hz | 
                                            
                                            
                                             
                                                12.5 kVA
                                             
                                         | 
                                    
| Rated operational power at AC-6B, 525 V, 50 Hz | 
                                            
                                            
                                             
                                                16.7 kVA
                                             
                                         | 
                                    
| Rated operational power at AC-6B, 690 V, 50 Hz | 
                                            
                                            
                                             
                                                20 kVA
                                             
                                         | 
                                    
| Switching capacity (auxiliary contacts, general use) | 
                                            
                                            
                                             
                                                10 A, 600 V AC, (UL/CSA)  
                                        1 A, 250 V DC, (UL/CSA)  | 
                                    
| Switching capacity (auxiliary contacts, pilot duty) | 
                                            
                                            
                                             
                                                P300, DC operated (UL/CSA)  
                                        A600, AC operated (UL/CSA)  | 
                                    
| Arcing time | 
                                            
                                            
                                             
                                                10 ms
                                             
                                         | 
                                    
| Drop-out voltage | 
                                            
                                            
                                             
                                                AC operated: 0.6 - 0.3 x UC, AC operated
                                             
                                         | 
                                    
| Duty factor | 
                                            
                                            
                                             
                                                100 %
                                             
                                         | 
                                    
| Pick-up voltage | 
                                            
                                            
                                             
                                                0.8 - 1.1 V AC x Uc
                                             
                                         | 
                                    
| Power consumption, pick-up, 50 Hz | 
                                            
                                            
                                             
                                                58 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
                                             
                                         | 
                                    
| Power consumption, pick-up, 60 Hz | 
                                            
                                            
                                             
                                                71 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
                                             
                                         | 
                                    
| Power consumption, sealing, 50 Hz | 
                                            
                                            
                                             
                                                7.6 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz  
                                        2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz  | 
                                    
| Power consumption, sealing, 60 Hz | 
                                            
                                            
                                             
                                                9.3 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz  
                                        2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz  | 
                                    
| Rated control supply voltage (Us) at AC, 50 Hz - min | 
                                            
                                            
                                             
                                                190 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 50 Hz - max | 
                                            
                                            
                                             
                                                190 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 60 Hz - min | 
                                            
                                            
                                             
                                                220 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 60 Hz - max | 
                                            
                                            
                                             
                                                220 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at DC - min | 
                                            
                                            
                                             
                                                0 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at DC - max | 
                                            
                                            
                                             
                                                0 V
                                             
                                         | 
                                    
| Switching time (AC operated, make contacts, closing delay) - min | 
                                            
                                            
                                             
                                                16 ms
                                             
                                         | 
                                    
| Switching time (AC operated, make contacts, closing delay) - max | 
                                            
                                            
                                             
                                                22 ms
                                             
                                         | 
                                    
| Switching time (AC operated, make contacts, opening delay) - min | 
                                            
                                            
                                             
                                                8 ms
                                             
                                         | 
                                    
| Switching time (AC operated, make contacts, opening delay) - max | 
                                            
                                            
                                             
                                                14 ms
                                             
                                         | 
                                    
| Making capacity without damping (I-peak value) | 
                                            
                                            
                                             
                                                180 x Ie
                                             
                                         | 
                                    
| Number of auxiliary contacts (normally closed contacts) | 
                                            
                                            
                                             
                                                1
                                             
                                         | 
                                    
| Number of auxiliary contacts (normally open contacts) | 
                                            
                                            
                                             
                                                1
                                             
                                         | 
                                    
| Number of contacts (normally closed) as main contact | 
                                            
                                            
                                             
                                                0
                                             
                                         | 
                                    
| Special purpose rating of capacitor switching | 
                                            
                                            
                                             
                                                7.5 kVar, 240 V 60 Hz 3phase, (UL/CSA)  
                                        14.4 A, 600 V 60 Hz 3phase, (UL/CSA) 18 A, 480 V 60 Hz 3phase, (UL/CSA) 15 kVar, 600 V 60 Hz 3phase, (UL/CSA) 15 kVar, 480 V 60 Hz 3phase, (UL/CSA) 18 A, 240 V 60 Hz 3phase, (UL/CSA)  | 
                                    
| Equipment heat dissipation, current-dependent Pvid | 
                                            
                                            
                                             
                                                2.1 W
                                             
                                         | 
                                    
| Heat dissipation capacity Pdiss | 
                                            
                                            
                                             
                                                0 W
                                             
                                         | 
                                    
| Heat dissipation per pole, current-dependent Pvid | 
                                            
                                            
                                             
                                                0.7 W
                                             
                                         | 
                                    
| Rated operational current for specified heat dissipation (In) | 
                                            
                                            
                                             
                                                18 A
                                             
                                         | 
                                    
| Static heat dissipation, non-current-dependent Pvs | 
                                            
                                            
                                             
                                                2.1 W
                                             
                                         | 
                                    
| 10.2.2 Corrosion resistance | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.5 Lifting | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.2.6 Mechanical impact | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.2.7 Inscriptions | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.3 Degree of protection of assemblies | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.4 Clearances and creepage distances | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.5 Protection against electric shock | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.6 Incorporation of switching devices and components | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.7 Internal electrical circuits and connections | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.8 Connections for external conductors | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.2 Power-frequency electric strength | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.3 Impulse withstand voltage | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.4 Testing of enclosures made of insulating material | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.10 Temperature rise | 
                                            
                                            
                                             
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             
                                         | 
                                    
| 10.11 Short-circuit rating | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             
                                         | 
                                    
| 10.12 Electromagnetic compatibility | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             
                                         | 
                                    
| 10.13 Mechanical function | 
                                            
                                            
                                             
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             
                                         |