Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 14 A, 5.5 kW, IP20/NEMA 0, Brake chopper, FS3 DC1-34014NB-A20CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185736
|
EAN |
4015081812356
|
Product Length/Depth |
175 mm
|
Product Height |
273 mm
|
Product Width |
129 mm
|
Product Weight |
6 kg
|
Certifications |
IEC/EN61800-3
EAC CUL UL File No.: E172143 UL Category Control No.: NMMS, NMMS7 CE UL report applies to both US and Canada Certified by UL for use in Canada CSA-C22.2 No. 14 UL RCM Specification for general requirements: IEC/EN 61800-2 UL 508C IEC/EN61800-5 RoHS, ISO 9001 UkrSEPRO IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5-1 |
Catalog Notes |
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
IGBT inverter
Brake chopper Control unit 7-digital display assembly Internal DC link PC connection Breaking resistance Additional PCB protection |
Functions |
4-quadrant operation possible
|
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
300 m, unscreened, with motor choke, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible, Motor feeder 100 m, screened, maximum permissible, Motor feeder |
Communication interface |
Modbus RTU, built in
SmartWire-DT, optional OP-Bus (RS485), built in CANopen®, built in |
Connection to SmartWire-DT |
In conjunction with DX-NET-SWD3 SmartWire DT module
Yes |
Degree of protection |
IP20
NEMA Other |
Frame size |
FS3
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
EtherNet/IP
CAN MODBUS Other bus systems |
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
96.2 % (η)
|
Input current ILN at 150% overload |
17.2 A
|
Leakage current at ground IPE - max |
12.7 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Speed control with slip compensation BLDC motors PM motors Synchronous reluctance motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Overload current IL at 150% overload |
21 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
14 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
5.5 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
20 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 V
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
11.3 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
14 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
10 HP
|
Apparent power at 400 V |
9.67 kVA
|
Apparent power at 480 V |
11.64 kVA
|
Braking resistance |
100 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Switch-on threshold for the braking transistor |
780 VDC
|
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Equipment heat dissipation, current-dependent Pvid |
209 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
14 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Heat dissipation details |
Operation (with 150 % overload)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|