Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 23 A, 11 kW, IP21/NEMA1, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9702-2001-00P
|
EAN |
4015081721405
|
Product Length/Depth |
244.7 mm
|
Product Height |
419 mm
|
Product Width |
167.8 mm
|
Product Weight |
10.7 kg
|
Certifications |
UkrSEPRO
CSA-C22.2 No. 274-13 RoHS, ISO 9001 UL UL Category Control No.: NMMS, NMMS7 C-Tick IEC/EN61800-5 Safety requirements: IEC/EN 61800-5 UL File No.: E134360 UL report applies to both US and Canada Certified by UL for use in Canada EAC CUL IEC/EN61800-3 Specification for general requirements: IEC/EN 61800-2 CE UL508 IEC/EN 61800-3 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Product Category |
Variable frequency drives
|
Features |
Tool-less swapping of fan
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Internal DC link
Multi-line graphic display Breaking resistance IGBT inverter Brake chopper Additional PCB protection PC connection Control unit DC link choke Radio interference suppression filter |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Operating mode |
Speed control with slip compensation
U/f control Torque regulation Sensorless vector control (SLV) |
Frame size |
FS2
|
Air volume capacity |
94 m³/h
|
Altitude |
Max. 3000 m
Above 1000 m with 1 % derating per 100 m Max. 2000 m for Corner Grounded TN Systems Max. 1000 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
21.5 kVA
|
Apparent power at 480 V |
26.8 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
29.3 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
21.7 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
18.5 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
15.75 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
DeviceNet, optional
Modbus TCP, built in BACnet MS/TP, built in Modbus RTU, built in CANopen®, optional PROFIBUS, optional SmartWire-DT, optional Ethernet IP, built in |
Converter type |
U converter
|
Degree of protection |
NEMA 1
IP21 |
Protocol |
CAN
Other bus systems PROFIBUS MODBUS PROFINET IO TCP/IP BACnet DeviceNet EtherNet/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
21 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
27 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
28.9 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
17.4 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
15 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload |
20 HP
|
Braking resistance |
42 Ω
|
Equipment heat dissipation, current-dependent Pvid |
421 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
29 A
|
Input current ILN at 150% overload |
21.5 A
|
Mains current distortion |
33.8 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
150 m, screened, maximum permissible, Motor feeder C3 ≤ 50 m, Radio interference level, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
500 V AC, 3-phase
400 V AC, 3-phase 480 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
421 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
98.2 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
9 mA
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
23 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
11 kW
|
Output at quadratic load at rated output voltage - max |
15 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
34.1 A
|
Overload current IL at 150% overload |
34.5 A
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
UPS drop test (for weights inside the UPS frame) Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
400 V AC, 3-phase
500 V AC, 3-phase 480 V AC, 3-phase |
Short-circuit protection rating |
35 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
31 A
|
Rated operational current (Ie) at 150% overload |
23 A
|
Rated operational current for specified heat dissipation (In) |
23 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
11 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload |
15 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
11 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
117 W at 25% current and 0% speed
127 W at 25% current and 50% speed 157 W at 100% current and 50% speed 179 W at 50% current and 50% speed 193 W at 50% current and 90% speed 240 W at 50% current and 0% speed 288 W at 100% current and 0% speed 379 W at 100% current and 90% speed |