Eaton Moeller series NZM - Molded Case Circuit Breaker. Remote operator, 208-240VAC, for size 3
| Product Name |
Eaton Moeller series NZM remote operator
|
| Catalog Number |
259850
|
| EAN |
4015082598501
|
| Product Length/Depth |
170 mm
|
| Product Height |
140 mm
|
| Product Width |
140 mm
|
| Product Weight |
3.155 kg
|
| Compliances |
UL/CSA
IEC RoHS conform |
| Certifications |
CSA (File No. 22086)
CE marking CSA (Class No. 1437-01) UL (File No. E140305) UL489 IEC60947 UL listed CSA certified CSA-C22.2 No. 5-09 UL (Category Control Number DIHS) |
| Model Code |
NZM3-XR208-240AC
|
| Type |
|
| Number of poles |
Three-pole/Four-pole
|
| Special features |
|
| Frame |
NZM3
|
| Used with |
NZM3(-4)
N(S)3(-4) |
| Voltage type |
AC
|
| Voltage rating |
208 - 240 V 50/60 Hz
|
| Operating voltage - min |
0.85 x Us
|
| Operating voltage - max |
1.1 x Us
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
208 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
208 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Voltage tolerance - min |
0.85
|
| Voltage tolerance - max |
1.1
|
| Rated operating frequency |
50 Hz
|
| Power consumption |
350 VA (110 - 130 V AC)
|
| Closing delay |
80 ms
|
| Breaking time |
1000 ms
|
| Number of operations per hour - max |
60
|
| Signal duration of remote operator at switch off - min |
250 ms
|
| Signal duration of remote operator at switch on - min |
30 ms
|
| Switch drive type |
Motor drive
|
| Special features |
|
| Lifespan, mechanical |
15000 operations
|
| Terminal capacity (solid/flexible conductor) |
18 - 14 AWG
0.75 mm² - 2.5 mm² with ferrule |
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|