Eaton’s Magnum DS low-voltage switchgear offers reliable protection and centralised control of low-voltage power circuits of up to 600 volts for a wide range of industries, including healthcare, data centres and petrochemical. Low-voltage switchgear is a metal-enclosed assembly with three-position, drawout power circuit breakers engineered to monitor and protect low-voltage electrical systems.
View images of Magnum DS low-voltage switchgear
When providing redundant power sources for critical power applications, specify the:
– Eaton ATC-900 controller for line-ups with main-main, main-generator or generator-generator applications
– Eaton PLC with Eaton touchscreen for automatic main-tie-main transfer
– Eaton Power Xpert™ dashboard to monitor or control transfer schemes for a main-tie-main and adjust settings and sequence details
| VOLTAGE |
Up to 600 V |
| CONTINUOUS MAIN BUS CURRENT | 1,600 A to 10,000 A |
| SHORT-CIRCUIT RESISTANCE | Up to 200,000 A |
| SHORT-TIME RESISTANCE | 30 cycles |
| CIRCUIT BREAKER AMPS | Up to 6,000 A |
| ANSI/IEEE | C37.20.1, C37.51 |
| UL |
1558, 1066 |
| CSA |
C22.2 No. 31-10 |
| OTHER CERTIFICATION | ABS |
| CONSTRUCTION |
Metal-enclosed |
| POWER TERMINATIONS | Rear access |
| INSULATING MEDIUM | Air |
| ENCLOSURE TYPE | NEMA 1 indoor, NEMA 3R outdoor |
| Standard Indoor Width Dimensions | 24 – 48 inches |
| Standard Indoor Depth Dimensions | 48 – 90 inches |
| Standard Indoor Height Dimensions | 90 inches |
| OVERCURRENT PROTECTION | Power circuit breaker, CSA C22.2 No. 268 |
| DEVICE MOUNTING | Drawout |
Modernise and extend the life of Magnum DS low-voltage switchgear with various accessories and common replacement parts