Eaton DC1 Variable frequency drive, 230 V AC, 1-phase, 7 A, 0.75 kW, IP66/NEMA 4X, Radio interference suppression filter, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199390
|
Model Code |
DC1-S27D0FN-A6SOE1
|
EAN |
4015081977796
|
Product Length/Depth |
162 mm
|
Product Height |
232 mm
|
Product Width |
161 mm
|
Product Weight |
2.5 kg
|
Certifications |
CE
CUL RCM RoHS, ISO 9001 UL 508C UL File No.: E172143 CE marking CSA-C22.2 No. 14 IEC/EN 61800-3 IEC/EN 61800-5-1 UL Category Control No.: NMMS, NMMS7 Certified by UL for use in Canada UL report applies to both US and Canada EAC IEC/EN61800-5 UL UkrSEPRO IEC/EN 61800-2 UL Listed |
Features |
Parameterization: Fieldbus
Parameterization: drivesConnect mobile (App) Parameterization: drivesConnect Parameterization: Keypad |
Fitted with: |
Control unit
Local controls UV resistance 7-digital display assembly PC connection IGBT inverter Internal DC link Radio interference suppression filter Additional PCB protection |
Cable length |
50 m, screened, maximum permissible, Motor feeder
75 m, unscreened, maximum permissible, Motor feeder 150 m, unscreened, with motor choke, maximum permissible, Motor feeder C1 ≤ 1 m, maximum motor cable length 100 m, screened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length |
Communication interface |
CANopen®, built in
Modbus RTU, built in OP-Bus (RS485), built in SmartWire-DT, optional |
Connection to SmartWire-DT |
No
|
Degree of protection |
NEMA 4X
IP66 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS1
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
EtherNet/IP
CAN MODBUS Other bus systems |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: for conducted emissions only |
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Max. 4000 m
Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Input current ILN at 150% overload |
9.3 A
|
Leakage current at ground IPE - max |
2.49 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
Speed control with slip compensation
Sensorless vector control (SLV) Synchronous reluctance motors PM motors U/f control BLDC motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
230 V AC, single-phase
240 V AC, single-phase |
Overload current IL at 150% overload |
10.5 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
7 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational voltage |
240 V AC, 1-phase
230 V AC, 1-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 V
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
6.8 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
7 A
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1 HP
|
Apparent power at 230 V |
1.61 kVA
|
Apparent power at 240 V |
1.68 kVA
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|