Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 520 A, 250 kW, IP00, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
3-4917-107A
|
EAN |
4015081941759
|
Product Length/Depth |
561 mm
|
Product Height |
980 mm
|
Product Width |
506 mm
|
Product Weight |
205 kg
|
Certifications |
IEC/EN 61800-3
RoHS, ISO 9001 Safety requirements: IEC/EN 61800-5 EAC C-Tick UL File No.: E134360 CE Specification for general requirements: IEC/EN 61800-2 UkrSEPRO CUL UL |
Product Category |
Variable frequency drives
|
Features |
Externally accessible fan
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Internal DC link
IGBT inverter Radio interference suppression filter DC link choke Multi-line graphic display Additional PCB protection Control unit PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
Sensorless vector control (SLV)
U/f control Speed control with slip compensation Torque regulation |
Frame size |
FS7
|
Air volume capacity |
1400 m³/h
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 3000 m Max. 2000 m for Corner Grounded TN Systems |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
408.8 kVA
|
Apparent power at 480 V |
511 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
550 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
437 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
65 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
108 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
BACnet MS/TP, built in CANopen®, optional DeviceNet, optional SmartWire-DT, optional PROFIBUS, optional Modbus TCP, built in Ethernet IP, built in |
Converter type |
U converter
|
Degree of protection |
IP00
NEMA Other |
Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
515 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
515 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
547 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
495.2 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz |
450 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
500 HP
|
Braking resistance |
1.4 Ω
|
Equipment heat dissipation, current-dependent Pvid |
7528 W
|
Input current ILN at 110% overload |
590 A
|
Input current ILN at 150% overload |
515 A
|
Mains current distortion |
28 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Adjustable to 150 % (I/Ie), DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 %, DC - Main circuit |
Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
50 m, screened, maximum permissible, Motor feeder C3 ≤ 50 m, Radio interference level, maximum motor cable length |
Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97.9 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
520 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
250 kW
|
Output at quadratic load at rated output voltage - max |
315 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
649 A
|
Overload current IL at 150% overload |
780 A
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
Short-circuit protection rating |
800 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
590 A
|
Rated operational current (Ie) at 150% overload |
520 A
|
Rated operational current for specified heat dissipation (In) |
520 A
|
Rated operational power at 380/400 V, 50 Hz |
250 kW
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
315 kW
|
Rated operational power at 500 V, 50 Hz |
355 kW
|
Rated operational power at 500 V, 50 Hz, 110% overload |
400 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|