Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 820 A, 450 kW, IP00, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
3-4918-108A
|
EAN |
4015081941698
|
Product Length/Depth |
561 mm
|
Product Height |
1538 mm
|
Product Width |
1037 mm
|
Product Weight |
820 kg
|
Certifications |
EAC
Specification for general requirements: IEC/EN 61800-2 CE UL Category Control No.: NMMS, NMMS7 RoHS, ISO 9001 UkrSEPRO CUL UL File No.: E134360 IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5 UL C-Tick |
Features |
Externally accessible fan
Temperature-controlled fan |
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
Fitted with: |
DC link choke
Brake chopper Internal DC link Multi-line graphic display IGBT inverter Radio interference suppression filter Additional PCB protection Breaking resistance Control unit PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Operating mode |
U/f control
Speed control with slip compensation Torque regulation Sensorless vector control (SLV) |
Frame size |
FS8
|
Air volume capacity |
2800 m³/h
|
Altitude |
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems Above 1000 m with 1 % derating per 100 m Max. 1000 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
637.4 kVA
|
Apparent power at 480 V |
796.7 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
900 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
769 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
65 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
215 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
Modbus TCP, built in
SmartWire-DT, optional Modbus RTU, built in DeviceNet, optional BACnet MS/TP, built in Ethernet IP, built in CANopen®, optional PROFIBUS, optional |
Converter type |
U converter
|
Degree of protection |
IP00
NEMA Other |
Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
775 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
775 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
855 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
770 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz |
700 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
800 HP
|
Braking resistance |
1.4 Ω
|
Equipment heat dissipation, current-dependent Pvid |
13190 W
|
Input current ILN at 110% overload |
916 A
|
Input current ILN at 150% overload |
815 A
|
Mains current distortion |
28 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Adjustable to 150 % (I/Ie), DC - Main circuit
Adjustable to 150 %, DC - Main circuit Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Cable length |
C3 ≤ 50 m, Radio interference level, maximum motor cable length
200 m, screened, maximum permissible, Motor feeder C2 ≤ 10 m, Radio interference level, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C1: with external filter, for conducted emissions only C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97.4 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
820 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
450 kW
|
Output at quadratic load at rated output voltage - max |
500 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
1012 A
|
Overload current IL at 150% overload |
1230 A
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
UPS drop test (for weights inside the UPS frame) Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
400 V AC, 3-phase
500 V AC, 3-phase 480 V AC, 3-phase |
Short-circuit protection rating |
2 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
920 A
|
Rated operational current (Ie) at 150% overload |
820 A
|
Rated operational current for specified heat dissipation (In) |
820 A
|
Rated operational power at 380/400 V, 50 Hz |
450 kW
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
500 kW
|
Rated operational power at 500 V, 50 Hz |
560 kW
|
Rated operational power at 500 V, 50 Hz, 110% overload |
630 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|