Eaton DG1 Variable frequency drive, 500 V AC, 3-phase, 18 A, 11 kW, IP21/NEMA1, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9703-2006-00P
|
EAN |
4015081772155
|
Product Length/Depth |
244.7 mm
|
Product Height |
419 mm
|
Product Width |
167.8 mm
|
Product Weight |
11.2 kg
|
Certifications |
UL
CE Safety requirements: IEC/EN 61800-5 UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 RoHS, ISO 9001 IEC/EN 61800-3 UL508 C-Tick CSA-C22.2 No. 274-13 IEC/EN61800-5 Certified by UL for use in Canada UL report applies to both US and Canada CUL UkrSEPRO EAC Specification for general requirements: IEC/EN 61800-2 IEC/EN61800-3 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Product Category |
Variable frequency drives
|
Features |
Tool-less swapping of fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Radio interference suppression filter
IGBT inverter Control unit DC link choke Breaking resistance Internal DC link Brake chopper Multi-line graphic display PC connection Additional PCB protection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
Torque regulation
Sensorless vector control (SLV) U/f control Speed control with slip compensation |
Frame size |
FS2
|
Air volume capacity |
94 m³/h
|
Altitude |
Max. 1000 m
Above 1000 m with 1 % derating per 100 m Max. 2000 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 600 V |
22.9 kVA
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Rated operational power at 525 V, 50 Hz, 3-phase |
11 kW
|
Rated operational power at 525 V, 50 Hz, 3-phase, 110% overload |
11 kW
|
Rated operational power at 600 V, 50 Hz, 3-phase |
11 kW
|
Rated operational power at 600 V, 50 Hz, 3-phase, 110% overload |
15 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
20.96 W
|
Switch-on threshold for the braking transistor |
1050 VDC
|
Voltage rating - max |
600 VAC
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
Ethernet IP, built in CANopen®, optional DeviceNet, optional SmartWire-DT, optional PROFIBUS, optional Modbus TCP, built in BACnet MS/TP, built in |
Converter type |
U converter
|
Degree of protection |
NEMA 1
IP21 |
Protocol |
TCP/IP
DeviceNet MODBUS Other bus systems PROFIBUS CAN PROFINET IO BACnet EtherNet/IP |
Assigned motor current IM at 525 V, 50 Hz, 110% overload |
17.4 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
17.4 A
|
Assigned motor current IM at 550 - 600 V, 60 Hz, 150% overload |
17 A
|
Assigned motor current IM at 600 V, 50 Hz, 110% overload |
20.4 A
|
Assigned motor current IM at 600 V, 50 Hz, 150% overload |
15.1 A
|
Assigned motor current IM at 600 V, 60 Hz, 110% overload |
17 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
15 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase, 110 % overload |
20 HP
|
Braking resistance |
30 Ω
|
Equipment heat dissipation, current-dependent Pvid |
391 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
20.4 A
|
Input current ILN at 150% overload |
16.7 A
|
Mains current distortion |
36.7 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Cable length |
150 m, screened, maximum permissible, Motor feeder
C3 ≤ 10 m, Radio interference level, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
600 V AC, 3-phase
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
391 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
98.2 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
9.8 mA
|
Mains voltage - max |
600 V
|
Mains voltage - min |
525 V
|
Nominal output current I2N |
18 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
11 kW
|
Output at quadratic load at rated output voltage - max |
15 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
600 V
|
Overload current IL at 110% overload |
24.2 A
|
Overload current IL at 150% overload |
27 A
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
600 V AC, 3-phase
|
Short-circuit protection rating |
35 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
22 A
|
Rated operational current (Ie) at 150% overload |
18 A
|
Rated operational current for specified heat dissipation (In) |
18 A
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
119 W at 100% current and 50% speed
146 W at 25% current and 50% speed 198 W at 100% current and 0% speed 198 W at 50% current and 50% speed 214 W at 50% current and 90% speed 345 W at 50% current and 0% speed 383 W at 100% current and 90% speed 94 W at 25% current and 0% speed |