Eaton Moeller® series MSC-D DOL starter, 380 V 400 V 415 V: 0.12, 0.18 kW, Ir= 0.4 - 0.63 A, 230 V 50 Hz, 240 V 60 Hz, AC voltage
| Product Name |
Eaton Moeller® series MSC-D DOL starter
|
| Catalog Number |
102739
|
| EAN |
4015081025886
|
| Product Length/Depth |
154 mm
|
| Product Height |
200 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.827 kg
|
| Certifications |
CSA File No.: 012528
IEC/EN 60947-4-1 CSA-C22.2 No. 14 (on request) UL60947-4-1A UL CSA UL 508 (on request) CE CSA Class No.: 3211-04 UL Category Control No.: NKJH UL File No.: E123500 CSA-C22.2 No. 14-10 |
| Model Code |
MSC-D-0,63-M7(230V50HZ)/BBA
|
| Fitted with: |
Short-circuit release
|
| Functions |
Temperature compensated overload protection
|
| Class |
CLASS 10 A
|
| Connection |
Screw terminals
|
| Connection to SmartWire-DT |
No
|
| Coordination type |
2
|
| Degree of protection |
IP20
NEMA Other |
| Model |
IEC/UL starter
|
| Mounting method |
Mounting on Busbar 60 mm
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
1
|
| Overload release current setting - min |
0.4 A
|
| Overload release current setting - max |
0.63 A
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Suitable for |
Also motors with efficiency class IE3
|
| Type |
Starter with Bi-Metal release
|
| Voltage type |
AC
|
| Altitude |
Max. 2000 m
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Rated operational current (Ie) |
0.6 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
0.63 A
|
| Rated operational power at AC-3, 220/230 V, 50 Hz |
0.09 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
0.18 kW
|
| Rated operational voltage |
230 - 415 V AC
|
| Switching capacity (auxiliary contacts, general use) |
15 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
| Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
50000 A
|
| Short-circuit release (Irm) - max |
9.8 A
|
| Power consumption, sealing, 50 Hz |
1.2 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Equipment heat dissipation, current-dependent Pvid |
5.7 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
1.9 W
|
| Rated operational current for specified heat dissipation (In) |
0.63 A
|
| Static heat dissipation, non-current-dependent Pvs |
1.4 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|