Eaton DA1 Variable frequency drive, 400 V AC, 3-phase, 46 A, 22 kW, IP55/NEMA 12, Radio interference suppression filter, OLED display
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
169393
|
EAN |
4015081658350
|
Product Length/Depth |
240 mm
|
Product Height |
450 mm
|
Product Width |
173 mm
|
Product Weight |
11.5 kg
|
Certifications |
UL 508C
CSA-C22.2 No. 14 UL IEC/EN61800-5 EAC CE UkrSEPRO Safety: EN 61800-5-1: 2003 UL File No.: E172143 CUL UL report applies to both US and Canada Certified by UL for use in Canada IEC/EN61800-3 DNV RCM Specification for general requirements: IEC/EN 61800-2 RoHS, ISO 9001 UL Category Control No.: NMMS, NMMS7 IEC/EN 61800-3 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DA1-34046FB-B55C
|
Cable length |
200 m, screened, with motor choke, maximum permissible, Motor feeder
100 m, screened, maximum permissible, Motor feeder C3 ≤ 25 m, Radio interference level, maximum motor cable length 300 m, unscreened, with motor choke, maximum permissible, Motor feeder C2 ≤ 5 m, Radio interference level, maximum motor cable length 150 m, unscreened, maximum permissible, Motor feeder |
Communication interface |
CANopen®, built in
PROFINET, optional Ethernet IP, optional PROFIBUS, optional DeviceNet, optional OP-Bus (RS485), built in Modbus RTU, built in Modbus-TCP, optional EtherCAT, optional SmartWire-DT, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
NEMA 12
IP55 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Fitted with: |
Control unit
OLED display Radio interference suppression filter Additional PCB protection Breaking resistance PC connection IGBT inverter Brake chopper Internal DC link |
Frame size |
FS4
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
CAN
PROFIBUS EtherNet/IP PROFINET IO DeviceNet MODBUS Other bus systems TCP/IP |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97.7 % (η)
|
Heat dissipation at current/speed |
192 W at 25% current and 0% speed
231 W at 25% current and 50% speed 261 W at 50% current and 0% speed 303 W at 50% current and 50% speed 350 W at 50% current and 90% speed 447 W at 100% current and 0% speed 527 W at 100% current and 50% speed 614 W at 100% current and 90% speed |
Input current ILN at 150% overload |
51.9 A
|
Leakage current at ground IPE - max |
2.47 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Speed control with slip compensation Optional: Vector control with feedback (CLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Overload current IL at 150% overload |
69 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
46 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
22 kW
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
70 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 VAC
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
41 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
40 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
30 HP
|
Apparent power at 400 V |
31.87 kVA
|
Apparent power at 480 V |
38.24 kVA
|
Braking resistance |
22 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
780 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
Equipment heat dissipation, current-dependent Pvid |
506 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
46 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|